2017-05-19 12:05:06JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1ST REVIEW: FBC 2014 5TH ED. RESIDENTIAL, AND 2011 NEC
  
 1) GENERAL SPACING OF THE OUTLETS IN THE UNIT ARE NOT
 PER CODE, MASTR BEDROOM, KITCHEN, LIVING ROOM
  
 E3901.2.1 SPACING.
 RECEPTACLES SHALL BE INSTALLED SO THAT NO POINT
 MEASURED HORIZONTALLY ALONG THE FLOOR LINE OF ANY WALL
 SPACE IS MORE THAN 6 FEET (1829
  
 E3901.2.2 WALL SPACE.
 AS USED IN THIS SECTION, A WALL SPACE SHALL INCLUDE THE
 FOLLOWING:
  
 1. ANY SPACE THAT IS 2 FEET (610 MM) OR MORE IN WIDTH,
 INCLUDING SPACE MEASURED AROUND CORNERS, AND THAT IS
 UNBROKEN ALONG THE
 FLOOR LINE BY DOORWAYS AND SIMILAR OPENINGS,
 FIREPLACES, AND FIXED CABINETS.
  
 2. THE SPACE OCCUPIED BY FIXED PANELS IN EXTERIOR
 WALLS, EXCLUDING SLIDING PANELS.
  
 3. THE SPACE CREATED BY FIXED ROOM DIVIDERS SUCH AS
 RAILINGS AND FREESTANDING BAR-TYPE COUNTERS.
  
 E3901.2.3 FLOOR RECEPTACLES.
 RECEPTACLE OUTLETS IN FLOORS SHALL NOT BE COUNTED AS
 PART OF THE REQUIRED NUMBER OF RECEPTACLE OUTLETS
 EXCEPT WHERE LOCATED WITHIN 18 INCHES (457 MM) OF THE
 WALL.
  
 2) SERVICE CALCULATION APPEARS TO HAVE COMMERCIAL
 ALLOWANCES NOT ALLOWED BY RESIDENTIAL CODE.
 PANEL SCHEDULE AND LOAD CALCULATION IS VERY SMALL AND
 HARD TO READ PLEASE MAKE THESE ITEMS LARGER ON
 RESUBMITTAL FOR REVIEW. ALTHOUGH THEY ARE IN A GREAT
 FROMAT
 THEY ARE TO SMAL TO READ.
  
 E3602.2 SERVICE LOAD.
 THE MINIMUM LOAD FOR UNGROUNDED SERVICE CONDUCTORS AND
 SERVICE DEVICES THAT SERVE 100 PERCENT OF THE DWELLING
 UNIT LOAD SHALL BE COMPUTED IN ACCORDANCE WITH
 TABLE E3602.2. UNGROUNDED SERVICE CONDUCTORS AND
 SERVICE DEVICES THAT SERVE LESS THAN 100 PERCENT OF THE
 DWELLING UNIT LOAD SHALL BE COMPUTED AS REQUIRED FOR
 FEEDERS IN ACCORDANCE WITH CHAPTER 37.
  
 3) SMOKE ALARMS AND CARBON MONOXIDE ALARMS NOT PER
 CODE.
  
 R314.2 SMOKE DETECTION SYSTEMS.
 HOUSEHOLD FIRE ALARM SYSTEMS INSTALLED IN ACCORDANCE
 WITH NFPA 72 THAT INCLUDE SMOKE ALARMS, OR A
 COMBINATION OF SMOKE DETECTOR AND AUDIBLE NOTIFICATION
 DEVICE
 INSTALLED AS REQUIRED BY THIS SECTION FOR SMOKE ALARMS,
 SHALL BE PERMITTED. THE HOUSEHOLD FIRE ALARM SYSTEM
 SHALL PROVIDE THE SAME LEVEL OF SMOKE DETECTION AND
 ALARM
 AS REQUIRED BY THIS SECTION FOR SMOKE ALARMS. WHERE A
 HOUSEHOLD FIRE WARNING SYSTEM IS INSTALLED USING A
 COMBINATION OF SMOKE DETECTOR AND AUDIBLE NOTIFICATION
 DEVICE(S), IT SHALL BECOME A PERMANENT FIXTURE OF THE
 OCCUPANCY AND OWNED BY THE HOMEOWNER. THE SYSTEM SHALL
 BE MONITORED BY AN APPROVED SUPERVISING STATION
 AND BE MAINTAINED IN ACCORDANCE WITH NFPA 72.
  
 EXCEPTION: WHERE SMOKE ALARMS ARE PROVIDED MEETING THE
 REQUIREMENTS OF SECTION R314.4.
  
 R314.3 LOCATION.
 SMOKE ALARMS SHALL BE INSTALLED IN THE FOLLOWING
 LOCATIONS:
  
 1. IN EACH SLEEPING ROOM.
  
 2. OUTSIDE EACH SEPARATE SLEEPING AREA IN THE IMMEDIATE
 VICINITY OF THE BEDROOMS.
  
 3. ON EACH ADDITIONAL STORY OF THE DWELLING, INCLUDING
 BASEMENTS AND HABITABLE ATTICS BUT NOT INCLUDING CRAWL
 SPACES AND UNINHABITABLE ATTICS. IN DWELLINGS OR
 DWELLING UNITS WITH SPLIT LEVELS AND WITHOUT AN
 INTERVENING DOOR BETWEEN THE ADJACENT LEVELS, A SMOKE
 ALARM INSTALLED ON THE UPPER LEVEL SHALL SUFFICE FOR
 THE ADJACENT LOWER LEVEL PROVIDED THAT THE LOWER LEVEL
 IS LESS THAN ONE FULL STORY BELOW THE UPPER LEVEL
  
 R315.1 CARBON MONOXIDE PROTECTION.
 EVERY SEPARATE BUILDING OR AN ADDITION TO AN EXISTING
 BUILDING FOR WHICH A PERMIT FOR NEW CONSTRUCTION IS
 ISSUED AND HAVING A FOSSIL-FUEL-BURNING HEATER OR
 APPLIANCE,
 A FIREPLACE, AN ATTACHED GARAGE, OR OTHER FEATURE,
 FIXTURE, OR ELEMENT THAT EMITS CARBON MONOXIDE AS
 BYPRODUCT OF COMBUSTION SHALL HAVE AN OPERATIONAL
 CARBON
 MONOXIDE ALARM INSTALLED WITHIN 10 FEET (3048 MM) OF
 EACH ROOM USED FOR SLEEPING PURPOSES.
  
 R315.1.1 CARBON MONOXIDE ALARM.
 THE REQUIREMENTS OF SECTION R315.1 SHALL BE SATISFIED
 BY PROVIDING FOR ONE OF THE FOLLOWING ALARM
 INSTALLATIONS:
  
 (1) A HARD-WIRED CARBON MONOXIDE ALARM.
  
 (2) A BATTERY-POWERED CARBON MONOXIDE ALARM.
  
 (3) A HARD-WIRED COMBINATION CARBON MONOXIDE AND SMOKE
 ALARM.
  
 (4) A BATTERY-POWERED COMBINATION CARBON MONOXIDE AND
 SMOKE ALARM.
  
 R315.1.2 COMBINATION ALARMS.
 COMBINATION SMOKE/CARBON MONOXIDE ALARMS SHALL BE
 LISTED AND LABELED BY A NATIONALLY RECOGNIZED TESTING
 LABORATORY.
  
  
  
  
  
  
  