2017-05-19 12:05:06 | JAKE LEAHY |
| ELECTRICAL PLANS EXAMINER II |
| 561-805-6713 |
| [email protected] |
| |
| 1ST REVIEW: FBC 2014 5TH ED. RESIDENTIAL, AND 2011 NEC |
| |
| 1) GENERAL SPACING OF THE OUTLETS IN THE UNIT ARE NOT |
| PER CODE, MASTR BEDROOM, KITCHEN, LIVING ROOM |
| |
| E3901.2.1 SPACING. |
| RECEPTACLES SHALL BE INSTALLED SO THAT NO POINT |
| MEASURED HORIZONTALLY ALONG THE FLOOR LINE OF ANY WALL |
| SPACE IS MORE THAN 6 FEET (1829 |
| |
| E3901.2.2 WALL SPACE. |
| AS USED IN THIS SECTION, A WALL SPACE SHALL INCLUDE THE |
| FOLLOWING: |
| |
| 1. ANY SPACE THAT IS 2 FEET (610 MM) OR MORE IN WIDTH, |
| INCLUDING SPACE MEASURED AROUND CORNERS, AND THAT IS |
| UNBROKEN ALONG THE |
| FLOOR LINE BY DOORWAYS AND SIMILAR OPENINGS, |
| FIREPLACES, AND FIXED CABINETS. |
| |
| 2. THE SPACE OCCUPIED BY FIXED PANELS IN EXTERIOR |
| WALLS, EXCLUDING SLIDING PANELS. |
| |
| 3. THE SPACE CREATED BY FIXED ROOM DIVIDERS SUCH AS |
| RAILINGS AND FREESTANDING BAR-TYPE COUNTERS. |
| |
| E3901.2.3 FLOOR RECEPTACLES. |
| RECEPTACLE OUTLETS IN FLOORS SHALL NOT BE COUNTED AS |
| PART OF THE REQUIRED NUMBER OF RECEPTACLE OUTLETS |
| EXCEPT WHERE LOCATED WITHIN 18 INCHES (457 MM) OF THE |
| WALL. |
| |
| 2) SERVICE CALCULATION APPEARS TO HAVE COMMERCIAL |
| ALLOWANCES NOT ALLOWED BY RESIDENTIAL CODE. |
| PANEL SCHEDULE AND LOAD CALCULATION IS VERY SMALL AND |
| HARD TO READ PLEASE MAKE THESE ITEMS LARGER ON |
| RESUBMITTAL FOR REVIEW. ALTHOUGH THEY ARE IN A GREAT |
| FROMAT |
| THEY ARE TO SMAL TO READ. |
| |
| E3602.2 SERVICE LOAD. |
| THE MINIMUM LOAD FOR UNGROUNDED SERVICE CONDUCTORS AND |
| SERVICE DEVICES THAT SERVE 100 PERCENT OF THE DWELLING |
| UNIT LOAD SHALL BE COMPUTED IN ACCORDANCE WITH |
| TABLE E3602.2. UNGROUNDED SERVICE CONDUCTORS AND |
| SERVICE DEVICES THAT SERVE LESS THAN 100 PERCENT OF THE |
| DWELLING UNIT LOAD SHALL BE COMPUTED AS REQUIRED FOR |
| FEEDERS IN ACCORDANCE WITH CHAPTER 37. |
| |
| 3) SMOKE ALARMS AND CARBON MONOXIDE ALARMS NOT PER |
| CODE. |
| |
| R314.2 SMOKE DETECTION SYSTEMS. |
| HOUSEHOLD FIRE ALARM SYSTEMS INSTALLED IN ACCORDANCE |
| WITH NFPA 72 THAT INCLUDE SMOKE ALARMS, OR A |
| COMBINATION OF SMOKE DETECTOR AND AUDIBLE NOTIFICATION |
| DEVICE |
| INSTALLED AS REQUIRED BY THIS SECTION FOR SMOKE ALARMS, |
| SHALL BE PERMITTED. THE HOUSEHOLD FIRE ALARM SYSTEM |
| SHALL PROVIDE THE SAME LEVEL OF SMOKE DETECTION AND |
| ALARM |
| AS REQUIRED BY THIS SECTION FOR SMOKE ALARMS. WHERE A |
| HOUSEHOLD FIRE WARNING SYSTEM IS INSTALLED USING A |
| COMBINATION OF SMOKE DETECTOR AND AUDIBLE NOTIFICATION |
| DEVICE(S), IT SHALL BECOME A PERMANENT FIXTURE OF THE |
| OCCUPANCY AND OWNED BY THE HOMEOWNER. THE SYSTEM SHALL |
| BE MONITORED BY AN APPROVED SUPERVISING STATION |
| AND BE MAINTAINED IN ACCORDANCE WITH NFPA 72. |
| |
| EXCEPTION: WHERE SMOKE ALARMS ARE PROVIDED MEETING THE |
| REQUIREMENTS OF SECTION R314.4. |
| |
| R314.3 LOCATION. |
| SMOKE ALARMS SHALL BE INSTALLED IN THE FOLLOWING |
| LOCATIONS: |
| |
| 1. IN EACH SLEEPING ROOM. |
| |
| 2. OUTSIDE EACH SEPARATE SLEEPING AREA IN THE IMMEDIATE |
| VICINITY OF THE BEDROOMS. |
| |
| 3. ON EACH ADDITIONAL STORY OF THE DWELLING, INCLUDING |
| BASEMENTS AND HABITABLE ATTICS BUT NOT INCLUDING CRAWL |
| SPACES AND UNINHABITABLE ATTICS. IN DWELLINGS OR |
| DWELLING UNITS WITH SPLIT LEVELS AND WITHOUT AN |
| INTERVENING DOOR BETWEEN THE ADJACENT LEVELS, A SMOKE |
| ALARM INSTALLED ON THE UPPER LEVEL SHALL SUFFICE FOR |
| THE ADJACENT LOWER LEVEL PROVIDED THAT THE LOWER LEVEL |
| IS LESS THAN ONE FULL STORY BELOW THE UPPER LEVEL |
| |
| R315.1 CARBON MONOXIDE PROTECTION. |
| EVERY SEPARATE BUILDING OR AN ADDITION TO AN EXISTING |
| BUILDING FOR WHICH A PERMIT FOR NEW CONSTRUCTION IS |
| ISSUED AND HAVING A FOSSIL-FUEL-BURNING HEATER OR |
| APPLIANCE, |
| A FIREPLACE, AN ATTACHED GARAGE, OR OTHER FEATURE, |
| FIXTURE, OR ELEMENT THAT EMITS CARBON MONOXIDE AS |
| BYPRODUCT OF COMBUSTION SHALL HAVE AN OPERATIONAL |
| CARBON |
| MONOXIDE ALARM INSTALLED WITHIN 10 FEET (3048 MM) OF |
| EACH ROOM USED FOR SLEEPING PURPOSES. |
| |
| R315.1.1 CARBON MONOXIDE ALARM. |
| THE REQUIREMENTS OF SECTION R315.1 SHALL BE SATISFIED |
| BY PROVIDING FOR ONE OF THE FOLLOWING ALARM |
| INSTALLATIONS: |
| |
| (1) A HARD-WIRED CARBON MONOXIDE ALARM. |
| |
| (2) A BATTERY-POWERED CARBON MONOXIDE ALARM. |
| |
| (3) A HARD-WIRED COMBINATION CARBON MONOXIDE AND SMOKE |
| ALARM. |
| |
| (4) A BATTERY-POWERED COMBINATION CARBON MONOXIDE AND |
| SMOKE ALARM. |
| |
| R315.1.2 COMBINATION ALARMS. |
| COMBINATION SMOKE/CARBON MONOXIDE ALARMS SHALL BE |
| LISTED AND LABELED BY A NATIONALLY RECOGNIZED TESTING |
| LABORATORY. |
| |
| |
| |
| |
| |
| |
| |