2017-05-18 15:37:22PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT TWO SETS OF A SITE DRAINAGE PLAN THAT
 COMPLIES WITH FBC-R R401.3. SURFACE DRAINAGE SHALL BE
 DIVERTED TO A STORM SEWER CONVEYANCE OR OTHER APPROVED
 POINT OF COLLECTION THAT DOES NOT CREATE A HAZARD. LOTS
 SHALL BE GRADED TO DRAIN SURFACE WATER AWAY FROM
 FOUNDATION WALLS. THE GRADE SHALL FALL A MINIMUM OF 6
 INCHES (152 MM) WITHIN THE FIRST 10 FEET (3048 MM).
 EXCEPTION: WHERE LOT LINES, WALLS, SLOPES OR OTHER
 PHYSICAL BARRIERS PROHIBIT 6 INCHES (152 MM) OF FALL
 WITHIN 10 FEET (3048 MM), DRAINS OR SWALES SHALL BE
 CONSTRUCTED TO ENSURE DRAINAGE AWAY FROM THE STRUCTURE.
 IMPERVIOUS SURFACES WITHIN 10 FEET (3048 MM) OF THE
 BUILDING FOUNDATION SHALL BE SLOPED A MINIMUM OF 2
 PERCENT AWAY FROM THE BUILDING.
  
 2) FBC 107.3.5.3 - INDICATE THE MEANS OF TERMITE
 PROTECTION PROPOSED PURSUANT TO FBC-R318.
  
 3) R1001.10 WHERE THE FIREPLACE OPENING IS 6 SQUARE
 FEET (0.6 M2) OR LARGER, THE HEARTH EXTENSION SHALL
 EXTEND AT LEAST 20 INCHES (508 MM) IN FRONT OF AND AT
 LEAST 12 INCHES (305 MM) BEYOND EACH SIDE OF THE
 FIREPLACE OPENING.
  
 4) SPECIFY THE HEIGHT OF THE CHIMNEY ABOVE THE ROOF ON
 THE PLANS. R1003.9 CHIMNEYS SHALL EXTEND AT LEAST 2
 FEET (610 MM) HIGHER THAN ANY PORTION OF A BUILDING
 WITHIN 10 FEET (3048 MM), BUT SHALL NOT BE LESS THAN 3
 FEET (914 MM) ABOVE THE HIGHEST POINT WHERE THE CHIMNEY
 PASSES THROUGH THE ROOF.
  
 5) SUBMIT TWO SETS OF MANUFACTURER'S SPECIFICATIONS
 WITH INSTALLATION REQUIREMENTS FOR THE 2 HR FIRE RATED
 INSULATED ALL-FUEL STAINLESS STEEL FLUE. FBC-R 1003.11
  
 6) SPECIFY THE DOOR TYPES FOR THE DOORS TO BEDROOMS 1
 AND 2 THAT ARE LOCATED IN W1-6 AND W1-8 ON THE PLANS.
 FBC 107.2.1
  
 7) SPECIFY THE DOOR TYPES FOR D1-1 AND D1-2. THEY WERE
 NOT IDENTIFIED ON THE PLANS. FBC 107.2.1
  
 8) THE ENERGY CALCULATIONS SPECIFY A VENTED ATTIC. SHOW
 COMPLIANCE WITH FBC-R806.1 VENTILATION REQUIRED.
 ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES FORMED WHERE
 CEILINGS ARE APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF
 RAFTERS SHALL HAVE CROSS VENTILATION FOR EACH SEPARATE
 SPACE BY VENTILATING OPENINGS PROTECTED AGAINST THE
 ENTRANCE OF RAIN OR SNOW. VENTILATION OPENINGS SHALL
 HAVE A LEAST DIMENSION OF 1/16 INCH (1.6 MM) MINIMUM
 AND 1/4 INCH (6.4 MM) MAXIMUM. VENTILATION OPENINGS
 HAVING A LEAST DIMENSION LARGER THAN 1/4 INCH (6.4 MM)
 SHALL BE PROVIDED WITH CORROSION-RESISTANT WIRE CLOTH
 SCREENING, HARDWARE CLOTH, OR SIMILAR MATERIAL WITH
 OPENINGS HAVING A LEAST DIMENSION OF 1/16 INCH (1.6 MM)
 MINIMUM AND 1/4 INCH (6.4 MM) MAXIMUM. OPENINGS IN ROOF
 FRAMING MEMBERS SHALL CONFORM TO THE REQUIREMENTS OF
 SECTION R802.1.8. REQUIRED VENTILATION OPENINGS SHALL
 OPEN DIRECTLY TO THE OUTSIDE AIR. R806.2 THE MINIMUM
 NET FREE VENTILATING AREA SHALL BE 1/150 OF THE AREA OF
 THE VENTED SPACE.
  
 9) PROVIDE SIZING CALCULATIONS, SPECIFY THE SIZE AND
 LOCATIONS OF THE OVERFLOW SCUPPERS. FBC-R903.4.1
 OVERFLOW DRAINS AND SCUPPERS. WHEN OTHER MEANS OF
 DRAINAGE OF OVERFLOW WATER IS NOT PROVIDED, OVERFLOW
 SCUPPERS SHALL BE PLACED IN WALLS OR PARAPETS NOT LESS
 THAN 2 INCHES (51 MM) NOR MORE THAN 4 INCHES (102 MM)
 ABOVE THE FINISHED ROOF COVERING AND SHALL BE LOCATED
 AS CLOSE AS PRACTICAL TO REQUIRED VERTICAL LEADERS OR
 DOWNSPOUTS OR WALL AND PARAPET SCUPPERS. AN OVERFLOW
 SCUPPER SHALL BE SIZED IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, PLUMBING. OVERFLOW DRAINS SHALL
 DISCHARGE TO AN APPROVED LOCATION AND SHALL NOT BE
 CONNECTED TO ROOF DRAIN LINES.
  
 10) THE ENERGY FORM R405 CONTAINS SOME ERRORS. FBC
 ENERGY CONSERVATION R101.5.1.1.2, R103.2 AND R405.4.2
 -THE NAME OF THE INDIVIDUAL COMPLETING THE COMPLIANCE
 REPORT IS REQUIRED.
 - THE RESIDENCE DOES NOT HAVE A METAL ROOF AS LISTED ON
 THE FORM UNDER ROOF MATERIALS.
 - THERE ARE THREE SEPARATE HEATING AND COOLING SYSTEMS.
 THE KBTU/HR HAVE BEEN COMBINED INTO ONE ON THE
 COMPLIANCE FORM.
 -THE SYSTEMS HAVE DIFFERENT SEERS AND NEED TO BE LISTED
 SEPARATELY IN ORDER TO SHOW THIS.
  
 11) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC
 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE
 BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER
 OF RECORD. PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH
 FL OR NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS
 AND MAXIMUM DESIGN PRESSURES FOR EACH OF THE DIFFERENT
 ROOFING MATERIALS, SKYLIGHTS, WINDOW/GLASS TYPES,
 STRUCTURAL MULLIONS AND EXTERIOR DOOR TYPES.
  
 12) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT
 A RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED.
  
  
  
  
  
  