Plan Review Notes
Plan Review Notes For Permit 17041105
Permit Number 17041105
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2017-05-01 13:04:16THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET T - A NOTE UNDER THE PROJECT CODE TABULAR
 SECTION INDICATES A OCCUPANY GROUP B (BUSINESS) - SELF
 SERVICE LAUNDRY. THE APPLICATION AND SCOPE OF WORK
 INDICATES A WHITE BOX.
  
 PLEASE CORRECT TO BUSINESS OCCUPANCY ONLY.
  
  
  
  
 2) SHEET T - A NOTE UNDER THE LIFE SAFETY SECTION
 INDICATES A NA ON THE LINE FOR EXIT REMOTENESS. THE
 CODE REFERENCE PROVIDED . 101 7.5.1.3 APPEARS TO BE AN
 INACCURATE CODE REFERENCE.
  
 PER NFPA 101, CHAPTER 39, EXISTING BUSINESS OCCUPANCIES
  
 39.2.4 NUMBER OF MEANS OF EGRESS.
  
 39.2.4.1 MEANS OF EGRESS SHALL COMPLY WITH ALL OF THE
 FOLLOWING, EXCEPT AS OTHERWISE PERMITTED BY 39.2.4.2
 THROUGH 39.2.4.6:
 (1) THE NUMBER OF MEANS OF EGRESS SHALL BE IN
 ACCORDANCE WITH 7.4.1.1 AND 7.4.1.3 THROUGH 7.4.1.6.
 (2) NOT LESS THAN TWO SEPARATE EXITS SHALL BE PROVIDED
 ON EVERY STORY.
 (3) NOT LESS THAN TWO SEPARATE EXITS SHALL BE
 ACCESSIBLE FROM EVERY PART OF EVERY STORY.
  
 39.2.4.2 EXIT ACCESS, AS REQUIRED BY 39.2.4.1(3), SHALL
 BE PERMITTED TO INCLUDE A SINGLE EXIT ACCESS PATH FOR
 THE DISTANCES PERMITTED AS COMMON PATHS OF TRAVEL BY
 39.2.5.3.
  
 39.2.4.3 A SINGLE EXIT SHALL BE PERMITTED FOR A ROOM OR
 AREA WITH A TOTAL OCCUPANCY LOAD OF LESS THAN 100
 PERSONS PROVIDED THAT ALL OF THE FOLLOWING CRITERIA ARE
 MET:
 (1) THE EXIT SHALL DISCHARGE DIRECTLY TO THE OUTSIDE AT
 THE LEVEL OF EXIT DISCHARGE FOR THE BUILDING.
 (2) THE TOTAL DISTANCE OF TRAVEL FROM ANY POINT,
 INCLUDING TRAVEL WITHIN THE EXIT, SHALL NOT EXCEED 100
 FT (30 M).
 (3) THE TOTAL DISTANCE OF TRAVEL SPECIFIED IN
 39.2.4.3(2) SHALL BE ON THE SAME STORY, OR, IF
 TRAVERSING OF STAIRS IS NECESSARY, SUCH STAIRS SHALL
 NOT EXCEED 15 FT (4570 MM) IN HEIGHT, AND BOTH OF THE
 FOLLOWING ALSO SHALL APPLY:
 (A) INTERIOR STAIRS SHALL BE PROVIDED WITH COMPLETE
 ENCLOSURES TO SEPARATE THEM FROM ANY OTHER PART OF THE
 BUILDING, WITH NO DOOR OPENINGS THEREIN.
 (B) A SINGLE OUTSIDE STAIR IN ACCORDANCE WITH 7.2.2
 SHALL BE PERMITTED TO SERVE ALL STORIES PERMITTED
 WITHIN THE 15 FT (4570 MM) VERTICAL TRAVEL LIMITATION.
  
 IF YOU BELIEVE YOUR OCCUPANCY MEETS ALL OF THE
 REQUIREMENTS PLEASE STATE IT AND CORRECT THE CODE
 REFERENCE.
  
  
  
  
 3) SHEET 1.0 & ALL OTHERS - THERE ARE NO DIMENSIONS
 PROVIDED ON ANY PLAN SHEET.
  
 PLEASE PROVIDE ACCURATE DIMENSION TO ALL AREAS.
  
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL