2017-05-01 13:04:16 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| |
| 1) SHEET T - A NOTE UNDER THE PROJECT CODE TABULAR |
| SECTION INDICATES A OCCUPANY GROUP B (BUSINESS) - SELF |
| SERVICE LAUNDRY. THE APPLICATION AND SCOPE OF WORK |
| INDICATES A WHITE BOX. |
| |
| PLEASE CORRECT TO BUSINESS OCCUPANCY ONLY. |
| |
| |
| |
| |
| 2) SHEET T - A NOTE UNDER THE LIFE SAFETY SECTION |
| INDICATES A NA ON THE LINE FOR EXIT REMOTENESS. THE |
| CODE REFERENCE PROVIDED . 101 7.5.1.3 APPEARS TO BE AN |
| INACCURATE CODE REFERENCE. |
| |
| PER NFPA 101, CHAPTER 39, EXISTING BUSINESS OCCUPANCIES |
| |
| 39.2.4 NUMBER OF MEANS OF EGRESS. |
| |
| 39.2.4.1 MEANS OF EGRESS SHALL COMPLY WITH ALL OF THE |
| FOLLOWING, EXCEPT AS OTHERWISE PERMITTED BY 39.2.4.2 |
| THROUGH 39.2.4.6: |
| (1) THE NUMBER OF MEANS OF EGRESS SHALL BE IN |
| ACCORDANCE WITH 7.4.1.1 AND 7.4.1.3 THROUGH 7.4.1.6. |
| (2) NOT LESS THAN TWO SEPARATE EXITS SHALL BE PROVIDED |
| ON EVERY STORY. |
| (3) NOT LESS THAN TWO SEPARATE EXITS SHALL BE |
| ACCESSIBLE FROM EVERY PART OF EVERY STORY. |
| |
| 39.2.4.2 EXIT ACCESS, AS REQUIRED BY 39.2.4.1(3), SHALL |
| BE PERMITTED TO INCLUDE A SINGLE EXIT ACCESS PATH FOR |
| THE DISTANCES PERMITTED AS COMMON PATHS OF TRAVEL BY |
| 39.2.5.3. |
| |
| 39.2.4.3 A SINGLE EXIT SHALL BE PERMITTED FOR A ROOM OR |
| AREA WITH A TOTAL OCCUPANCY LOAD OF LESS THAN 100 |
| PERSONS PROVIDED THAT ALL OF THE FOLLOWING CRITERIA ARE |
| MET: |
| (1) THE EXIT SHALL DISCHARGE DIRECTLY TO THE OUTSIDE AT |
| THE LEVEL OF EXIT DISCHARGE FOR THE BUILDING. |
| (2) THE TOTAL DISTANCE OF TRAVEL FROM ANY POINT, |
| INCLUDING TRAVEL WITHIN THE EXIT, SHALL NOT EXCEED 100 |
| FT (30 M). |
| (3) THE TOTAL DISTANCE OF TRAVEL SPECIFIED IN |
| 39.2.4.3(2) SHALL BE ON THE SAME STORY, OR, IF |
| TRAVERSING OF STAIRS IS NECESSARY, SUCH STAIRS SHALL |
| NOT EXCEED 15 FT (4570 MM) IN HEIGHT, AND BOTH OF THE |
| FOLLOWING ALSO SHALL APPLY: |
| (A) INTERIOR STAIRS SHALL BE PROVIDED WITH COMPLETE |
| ENCLOSURES TO SEPARATE THEM FROM ANY OTHER PART OF THE |
| BUILDING, WITH NO DOOR OPENINGS THEREIN. |
| (B) A SINGLE OUTSIDE STAIR IN ACCORDANCE WITH 7.2.2 |
| SHALL BE PERMITTED TO SERVE ALL STORIES PERMITTED |
| WITHIN THE 15 FT (4570 MM) VERTICAL TRAVEL LIMITATION. |
| |
| IF YOU BELIEVE YOUR OCCUPANCY MEETS ALL OF THE |
| REQUIREMENTS PLEASE STATE IT AND CORRECT THE CODE |
| REFERENCE. |
| |
| |
| |
| |
| 3) SHEET 1.0 & ALL OTHERS - THERE ARE NO DIMENSIONS |
| PROVIDED ON ANY PLAN SHEET. |
| |
| PLEASE PROVIDE ACCURATE DIMENSION TO ALL AREAS. |
| |
| |
| |
| 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| |
| |
| 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| |
| PETER LEDUC |
| FIRE MARSHAL |
| 561-804-4709 |
| [email protected] |
| |
| |