2017-05-09 09:29:32 | BUILDING PLAN REVIEW |
| 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1 |
| ADMINISTRATION |
| |
| CHRISTOPHER S. THROOP, C.B.O. |
| PLANS EXAMINER, PX3169 |
| CONSTRUCTION SERVICES DIVISION |
| TEL: 561-805-6726 |
| FAX: 561-805-6676 |
| |
| 1ST REVIEW |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| |
| STRUCTURE IS POST FIRM ? CONSTRUCTED AFTER 03/01 1979 |
| |
| 1. FLOOD ZONE A5 |
| 2. BASE FLOOD ELEVATION (BFE) - 7.0 FEET |
| 3. DESIGN FLOOD ELEVATION (DFE) ? 8.0 FEET |
| 4. ELEVATOR SHALL BE DESIGNED AND INSTALLED PER THE |
| FOLLOWING: |
| 4A. 2014 FBC RESIDENTIAL ? SECTION R322 FLOOD RESISTANT |
| CONSTRUCTION. |
| 4B. ASCE 24-05 FLOOD RESISTANT DESIGN AND CONSTRUCTION |
| 4C. FEMA TECHNICAL BULLETIN 4 ELEVATOR INSTALLATION |
| 4D. ASME A17.1-2007 SAFETY CODE FOR ELEVATORS AND |
| ESCALATORS |
| 5. ELEVATION CERTIFICATE DATED 09/14/2016 ON-FILE REF. |
| MASTER 16050108 |
| 6. YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| BELOW. |
| 6A. PROVIDE FLOOR PLAN IDENTIFYING LOCATION OF ELEVATOR |
| AND EQUIPMENT. |
| 6B. PROVIDE ELEVATION PLAN IDENTIFYING ELEVATIONS OF |
| ALL COMPONENTS OF ELEVATOR. |
| 6C. PROVIDE MANUFACTURER?S INSTALLATION INSTRUCTIONS. |
| |
| DUE TO THE DEFICIENCIES OF THIS PLAN, A COMPLETE AND |
| THOROUGH REVIEW CANNOT BE PERFORMED AT THIS TIME. UPON |
| RE-SUBMITTAL, ADDITIONAL COMMENTS MAY BE MADE. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY |
| REVIEWED SHEETS DETACHED AND MARK VOID. |
| |
| |