Plan Review Notes
Plan Review Notes For Permit 17041075
Permit Number 17041075
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2017-04-28 08:02:144/28/2017 FAIL - PROVIDE PROPER PLANS AND DOCUMENTATION
 FOR FIRE ALARM SYSTEM. PLEASE PROVIDE:
 1. PLANS SHOWING NUMBER, ADDRESSES, AND LOCATIONS OF
 DEVICES
 2. LETTER OF COMPATIBILTY FOR EXISTING DEVICES IN
 RELATION TO NEW FACP.
 3. BATTERY CALCULATIONS.
 4. 4 TIMES THE FEE DUE TO PANEL INSTALL WITHOUT PERMIT.
  
  
 SENT TO ELECTRICAL