2017-04-27 14:55:08 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| |
| |
| 1) THE IS NO TITLE BLOCK ON THE SUBMITTED SHEET THAT |
| INCLUDE THE ADDRESS, APT # AND DESIGN PROFESSIONAL. |
| |
| PLEASE CORRECT. |
| |
| |
| |
| |
| 2) THE PRINT IS TOO SMALL AND UNREADABLE IN SOME AREAS. |
| |
| PLEASE ENLARGE |
| |
| |
| |
| |
| 3) THERE IS APPEARS TO WALLS BEING REMOVED AND CEILING |
| WORK PROPOSED IN THE KITCHEN AREA. |
| |
| IT IS UNCLEAR WHAT IS EXSITING AND WHAT IS NEW. |
| |
| PLEASE CLARIFY OR PROVIDE BETTER DETAIL. |
| |
| |
| |
| |
| 4) ANY REMOVAL OR CONSTRUCTION OF NEW WALLS OR CEILING |
| SPACES REQUIRES AN EVALUATION OF THE FIRE SPRINKLER |
| COVERAGE AND PROTECTION. THERE IS NO INDICATION OF |
| EXISTING SPRINKLERS OR ANY WORK BEING DONE. |
| |
| ANY FIRE SPRINKLER OR FIRE ALARM WORK SHALL BE DONE |
| UNDER SEPARATE SHOP DRAWINGS BY CERTIFIED LIFE SAFETY |
| CONTRACTORS. |
| |
| PLEASE PROVIDE AN APPLICABLE NOTE OF ALL APPLICABLE |
| INFORMATION AND COMPLIANCE. |
| |
| |
| |
| |
| 5) THERE APPEAR TO BE BE NEW WORK IN THE BATHROOM |
| CEILING AREA. |
| |
| IT IS UNCLEAR WHAT IS EXSITING AND WHAT IS NEW. |
| |
| PLEASE CLARIFY OR PROVIDE BETTER DETAIL. |
| |
| |
| |
| |
| 6) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| |
| |
| 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| |
| |