Plan Review Notes
Plan Review Notes For Permit 17041058
Permit Number 17041058
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2017-04-27 14:55:08THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) THE IS NO TITLE BLOCK ON THE SUBMITTED SHEET THAT
 INCLUDE THE ADDRESS, APT # AND DESIGN PROFESSIONAL.
  
 PLEASE CORRECT.
  
  
  
  
 2) THE PRINT IS TOO SMALL AND UNREADABLE IN SOME AREAS.
  
 PLEASE ENLARGE
  
  
  
  
 3) THERE IS APPEARS TO WALLS BEING REMOVED AND CEILING
 WORK PROPOSED IN THE KITCHEN AREA.
  
 IT IS UNCLEAR WHAT IS EXSITING AND WHAT IS NEW.
  
 PLEASE CLARIFY OR PROVIDE BETTER DETAIL.
  
  
  
  
 4) ANY REMOVAL OR CONSTRUCTION OF NEW WALLS OR CEILING
 SPACES REQUIRES AN EVALUATION OF THE FIRE SPRINKLER
 COVERAGE AND PROTECTION. THERE IS NO INDICATION OF
 EXISTING SPRINKLERS OR ANY WORK BEING DONE.
  
 ANY FIRE SPRINKLER OR FIRE ALARM WORK SHALL BE DONE
 UNDER SEPARATE SHOP DRAWINGS BY CERTIFIED LIFE SAFETY
 CONTRACTORS.
  
 PLEASE PROVIDE AN APPLICABLE NOTE OF ALL APPLICABLE
 INFORMATION AND COMPLIANCE.
  
  
  
  
 5) THERE APPEAR TO BE BE NEW WORK IN THE BATHROOM
 CEILING AREA.
  
 IT IS UNCLEAR WHAT IS EXSITING AND WHAT IS NEW.
  
 PLEASE CLARIFY OR PROVIDE BETTER DETAIL.
  
  
  
  
 6) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  