2017-05-04 12:18:16 | 2014 FBC- BUILDING PLAN REVIEW |
| W. P. B. REVISION: 17041051 |
| W. P. B. PERMIT: 16080044 |
| ADD: 324 DATURA ST./ 1ST FLOOR LOBBY |
| CONT: GERALD CONTRACTING |
| TEL: 561-832-9785 |
| E-MAIL: [email protected] |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: THURS. MAY 04/2017 |
| ACTION: DENIED |
| |
| THE REVISION OF THE 1ST FLOOR LOBBY AND ATRIUM AREA |
| SHOWS THE WON DOOR BEING REMOVED AND BI-SWING GLAZED |
| DOORS AND SIDE LIGHT BEING INSTALLED. THE 2014 FBC-B |
| SECTION 404.6 DESCRIBES THE REQUIREMENTS FOR 1 HOUR |
| FIRE BARRIERS, GLASS WALL PANELS AND THE DOORS HAVING |
| TO COMPLY WITH FBC-B TABLE 716.5. |
| |
| THE FLOOR PLAN A-1.0 SHOWS THE NEW DOORS IDENTIFIED AS |
| ?B?. THE DOOR SCHEDULE FOR TYPE B ILLUSTRATIONS B1 AND |
| B2 BOTH SHOW SOLID CORE DOORS, NO GLAZING. TABLE 716.5 |
| FOR OTHER FIRE BARRIER (NOTE LISTED UNDER FIRE BARRIERS |
| AS SHAFTS, EXIT ACCESS STAIRWAYS) REQUIRES ? HOUR |
| ASSEMBLY , VISION PANEL MAXIMUM SIZE TESTED AND THE |
| VISION PANEL GLAZING MARKED WITH D-H-NT-45 AND |
| SIDELIGHT WITH THE SAME MARKINGS. |
| |
| THE OTHER ISSUES WITH THE SIDE LIGHT WOULD BE FOUND |
| UNDER 404.6 EXCEPTIONS ; |
| |
| 1. A FIRE BARRIER IS NOT REQUIRED WHERE A GLASS WALL |
| FORMING A SMOKE PARTITION IS PROVIDED. THE GLASS WALL |
| SHALL COMPLY WITH ALL OF THE FOLLOWING: |
| |
| 1.1. AUTOMATIC SPRINKLERS ARE PROVIDED ALONG BOTH SIDES |
| OF THE SEPARATION WALL AND DOORS, OR ON THE ROOM SIDE |
| ONLY IF THERE IS NOT A WALKWAY ON THE ATRIUM SIDE. THE |
| SPRINKLERS SHALL BE LOCATED BETWEEN 4 INCHES AND 12 |
| INCHES (102 MM AND 305 MM) AWAY FROM THE GLASS AND AT |
| INTERVALS ALONG THE GLASS NOT GREATER THAN 6 FEET (1829 |
| MM). THE SPRINKLER SYSTEM SHALL BE DESIGNED SO THAT THE |
| ENTIRE SURFACE OF THE GLASS IS WET UPON ACTIVATION OF |
| THE SPRINKLER SYSTEM WITHOUT OBSTRUCTION; |
| |
| 1.2. THE GLASS WALL SHALL BE INSTALLED IN A GASKETED |
| FRAME IN A MANNER THAT THE FRAMING SYSTEM DEFLECTS |
| WITHOUT BREAKING (LOADING) THE GLASS BEFORE THE |
| SPRINKLER SYSTEM OPERATES; AND |
| |
| 1.3. WHERE GLASS DOORS ARE PROVIDED IN THE GLASS WALL, |
| THEY SHALL BE EITHER SELF-CLOSING OR AUTOMATIC-CLOSING. |
| |
| 2) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| JAMES A. WITMER BN, PX, CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES |
| DEPARTMENT |
| 401 CLEMATIS ST. |
| WEST PALM BEACH. FL 33402 |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| DEVELOPMENT SERVICES HOME PAGE |
| HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| |
| PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| |
| |
| |
| |
| |