Plan Review Notes
Plan Review Notes For Permit 17041031
Permit Number 17041031
Review Stop M
Sequence Number 1
Notes
Date Text
2017-04-27 15:16:471ST REVIEW FBC-2014 MECHANICAL
 REVISION #17041031
 MASTER #14120431
 4/27/17
  
 1) SHEET M-4.03: THE PLAN INDICATES THE TRASH ROOM
 EXHAUST FAN HAS BEEN RELOCATED APPARENTLY TO THE ROOF.
 PLEASE REVISE THE PLANS TO SHOW THE LOCATION OF THE FAN
 AND WHATEVER CHANGES HAVE BEEN MADE TO THE FAN
 EQUIPMENT SCHEDULE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  