Plan Review Notes
Plan Review Notes For Permit 17040955
Permit Number 17040955
Review Stop M
Sequence Number 1
Notes
Date Text
2017-04-25 16:09:311ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17040955
 4/25/17
  
 1) THE REVISED PLAN SHOWS DUCTWORK FROM AHU'S #9 & 11
 PENETRATING INTO THE INTERIOR EXIT STAIRWAYS WHICH IS
 PROHIBITED PER SECTION 1022.6 FBC-14 BUILDING. THE
 ORIGINAL PLAN SHOWED INDEPENDENT SYSTEMS #16 & 17
 OPERATING IN THE STAIRWAYS WHICH HAVE NOW BEEN
 ELIMINATED- PLEASE CORRECT.
  
 2) THE REVISED PLAN SHOWS A NEW SPLIT SYSTEM WHICH IS
 ALSO LABELED #18 LIKE THE EXISTING HEAT PUMP AHU.
 PLEASE SHOW THE LOCATION OF THE NEW SYSTEM AND PROVIDE
 AC COOLING AND HEATING CALCULATIONS IN COMPLIANCE WITH
 SECTION C403.2.1 FBC-14 ENERGY CONSERVATION.
  
 3) REVISE THE ENERGY CALCULATIONS TO INCORPORATE THE
 CHANGES TO THE APPROVED AC SYSTEMS.
  
 4) PROVIDE A NARRATIVE FRROM THE DESIGN PROFESSIONAL
 ITEMIZING ALL CHANGES TO THE APPROVED MECHANICAL PLANS,
 AND ALL CORRECTIONS MADE TO THE NEW REVISED PLANS.
  