2017-06-20 15:15:30 
 2ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17040865
 6/20/17
  
 COMMENT #6 FROM THE 1ST REVIEW STILL EXISTS. I HAVE
 REPRINTED IT BELOW. IF THE INTENTION IS TO MODIFIY THE
 EXISTING SUPPORT STRUCTURE ON THE ROOF TO SUPPORT THE
 NEW CONDENSER, PLEASE PROVIDE COMPLETE DETAILS AND EDIT
 THE NOTE ON M3.0 THAT IS SPECIFYING A NEW STAND.
  
 6) THE ARCHITECTURAL AND STRUCTURAL PLANS ARE
 CONFLICTING WITH THE MECHANICAL PLAN AS TO HOW THE NEW
 ACCU-1 WILL BE MOUNTED ON THE ROOF- SEE A-111.00,
 S-301, AND M3.0. IF USING THE STAND, PLEASE PROVIDE TWO
 COPIES OF THE NOA BEARING THE APPROVAL STAMP OF THE
 EOR. THE EOR SHALL ALSO CIRCLE, HIGHLIGHT, OR OTHERWISE
 MARK ALL APPLICABLE NOTES, DETAILS, FASTENERS , AND
 DESIGN
  
 PRESSURE TABLES ETC.THAT PERTAIN TO THE INSTALLATION.
 SEE ALSO TABLE 1509.6.5 FBC-14 BUILDING AND SHOW THE
 CLEARANCE HEIGHT FROM THE ROOM SURFACE TO THE BOTTOM OF
 THE CU.
  