2017-06-20 15:15:30 | | | 2ND REVIEW FBC-2014 MECHANICAL | | PERMIT #17040865 | | 6/20/17 | | | | COMMENT #6 FROM THE 1ST REVIEW STILL EXISTS. I HAVE | | REPRINTED IT BELOW. IF THE INTENTION IS TO MODIFIY THE | | EXISTING SUPPORT STRUCTURE ON THE ROOF TO SUPPORT THE | | NEW CONDENSER, PLEASE PROVIDE COMPLETE DETAILS AND EDIT | | THE NOTE ON M3.0 THAT IS SPECIFYING A NEW STAND. | | | | 6) THE ARCHITECTURAL AND STRUCTURAL PLANS ARE | | CONFLICTING WITH THE MECHANICAL PLAN AS TO HOW THE NEW | | ACCU-1 WILL BE MOUNTED ON THE ROOF- SEE A-111.00, | | S-301, AND M3.0. IF USING THE STAND, PLEASE PROVIDE TWO | | COPIES OF THE NOA BEARING THE APPROVAL STAMP OF THE | | EOR. THE EOR SHALL ALSO CIRCLE, HIGHLIGHT, OR OTHERWISE | | MARK ALL APPLICABLE NOTES, DETAILS, FASTENERS , AND | | DESIGN | | | | PRESSURE TABLES ETC.THAT PERTAIN TO THE INSTALLATION. | | SEE ALSO TABLE 1509.6.5 FBC-14 BUILDING AND SHOW THE | | CLEARANCE HEIGHT FROM THE ROOM SURFACE TO THE BOTTOM OF | | THE CU. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|