Plan Review Notes
Plan Review Notes For Permit 17040865
Permit Number 17040865
Review Stop P
Sequence Number 1
Notes
Date Text
2017-05-17 16:40:451ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. SHOW KNEE AND TOE CLEARANCE FOR LAVATORY. PER FBC
 ACC 606.2
  
 2. GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL
 POSITION, 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915
 MM) MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP
 OF THE GRIPPING SURFACE. PER FBC ACC 609.4
  
 3. ROOM 28 P-TLT THE TOP FOR THE LAVATORY CAN NOT
 ENCROACH INTO THE CLEAR FLOOR SPACE OF THE TOILET. PER
 FBC ACC 604.3.1, 604.3.2,
  
 4. SHT. P0.1 DETAIL P1 A VACUUM RELIEF VALVE IS
 REQUIRED ON A BOTTOM FED WATER HEATER .PER FBC PL 504.2
  
 5. THE BREAKROOM SINK, THE SINK IN THE WAITING ROOM AND
 A MIN OF ONE SINK IN ONE OF THE EXAM ROOMS SHALL COMPLY
 WITH FBC ACC 606, 212.3 SINKS.
 WHERE SINKS ARE PROVIDED, AT LEAST 5 PERCENT, BUT NO
 FEWER THAN ONE, OF EACH TYPE PROVIDED IN EACH
 ACCESSIBLE ROOM OR SPACE SHALL COMPLY WITH 606.
  
 6. THE WATER FOUNTAIN SHALL COMPLY WITH FBC ACC 602.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  