2017-05-17 16:40:45 | 1ST REVIEW |
| |
| GEORGE JOHNSON |
| PLUMBING PLANS EXAMINER LL |
| CITY OF WEST PALM BEACH |
| DEVELOPMENT SERVICES |
| BUILDING DIVISION |
| 561-805-6711 |
| [email protected] |
| |
| PLUMBING COMMENTS: |
| |
| 1. SHOW KNEE AND TOE CLEARANCE FOR LAVATORY. PER FBC |
| ACC 606.2 |
| |
| 2. GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL |
| POSITION, 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 |
| MM) MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP |
| OF THE GRIPPING SURFACE. PER FBC ACC 609.4 |
| |
| 3. ROOM 28 P-TLT THE TOP FOR THE LAVATORY CAN NOT |
| ENCROACH INTO THE CLEAR FLOOR SPACE OF THE TOILET. PER |
| FBC ACC 604.3.1, 604.3.2, |
| |
| 4. SHT. P0.1 DETAIL P1 A VACUUM RELIEF VALVE IS |
| REQUIRED ON A BOTTOM FED WATER HEATER .PER FBC PL 504.2 |
| |
| 5. THE BREAKROOM SINK, THE SINK IN THE WAITING ROOM AND |
| A MIN OF ONE SINK IN ONE OF THE EXAM ROOMS SHALL COMPLY |
| WITH FBC ACC 606, 212.3 SINKS. |
| WHERE SINKS ARE PROVIDED, AT LEAST 5 PERCENT, BUT NO |
| FEWER THAN ONE, OF EACH TYPE PROVIDED IN EACH |
| ACCESSIBLE ROOM OR SPACE SHALL COMPLY WITH 606. |
| |
| 6. THE WATER FOUNTAIN SHALL COMPLY WITH FBC ACC 602. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |
| WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES |
| AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE |
| AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW. |
| |