2017-04-25 11:50:191ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17040865
 4/25/17
  
 1) SHEET G-040.00: THE PROPOSED PROJECT IS CLASSIFIED
 AS A CHANGE OF OCCUPANCY AS DEFINED BY SECTION 202
 FBC-14 EXISTING BUILDING CODE. PLEASE ADD THE REQUIRED
 CODE DATA TO THE GENERAL PROJECT INFORMATION.
  
 2) REVISE THE ENERGY CALCULATIONS TO INDICATE CHANGE OF
 OCCUPANCY UNDER BUILDING CLASSIFICATION.
  
 3) M0.1: PROVIDE EXHAUST VENTILATION CALCULATIONS FOR
 THE TOILET ROOMS AND THE ELECTRICAL AND SOILED ROOMS.
 PLEASE INDICATE HOW THE FANS WILL OPERATE- CONTINUOSLY
 OR INTERMITTENTLY.
  
 4) SHEET M1.1: IT APPEARS RETURN GRILLS ARE MISSING IN
 THE CEILINGS OF OFFICES # 25, 26, 27, 32, 33 & STAFF
 LOUNGE #41.
  
 5) M1.1: PLEASE LABEL THE CONDENSER SHOWN IN THE 2ND
 FLOOR PLAN. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR
 THE CONDENSER THAT INDICATE IT CAN BE INSTALLED ON THE
 INTERIOR OF THE BUILDING.
  
 6) THE ARCHITECTURAL AND STRUCTURAL PLANS ARE
 CONFLICTING WITH THE MECHANICAL PLAN AS TO HOW THE NEW
 ACCU-1 WILL BE MOUNTED ON THE ROOF- SEE A-111.00,
 S-301, AND M3.0. IF USING THE STAND, PLEASE PROVIDE TWO
 COPIES OF THE NOA BEARING THE APPROVAL STAMP OF THE
 EOR. THE EOR SHALL ALSO CIRCLE, HIGHLIGHT, OR OTHERWISE
 MARK ALL APPLICABLE NOTES, DETAILS, FASTENERS , AND
 DESIGN
  
 PRESSURE TABLES ETC.THAT PERTAIN TO THE INSTALLATION.
 SEE ALSO TABLE 1509.6.5 FBC-14 BUILDING AND SHOW THE
 CLEARANCE HEIGHT FROM THE ROOM SURFACE TO THE BOTTOM OF
 THE CU.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  