Plan Review Notes
Plan Review Notes For Permit 17040825
Permit Number 17040825
Review Stop M
Sequence Number 1
Notes
Date Text
2017-04-21 16:40:511ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17040825
 4/21/17
  
 1) EXHAUST VENTILATION AT A RATE 100 CFMS PER SQ. FT.
 IS REQUIRED FOR THE KITCHEN IF USING A VENT HOOD
 INTERMITTENTLY- TABLE 403.3. PLEASE PROVIDE AN
 EQUIPMENT SCHEDULE ON THE PLAN THAT SHOWS THE MAKE AND
 MODEL AND VENTING CAPACITY OF THE HOOD, AND SUBMIT
 MANUFACTURER'S SPECIFICATIONS. REFER TO SECTION 505.2-
 MAKEUP AIR MAY BE REQUIRED.
  
 2) INDICATE THE TYPE AND SIZE OF EXHAUST DUCT, SHOW THE
 DUCT RUN AND TERMINATION LOCATION.
  
 3) PROVIDE A SCOPE OF WORK FOR AC ALTERATIONS ON THE
 PLAN WITH CORRELATING DRAWINGS AND DETAILS (IF
 APPLICABLE TO THE PROJECT).
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved