2017-04-24 12:04:00 | RESIDENTIAL MASTER FOR ROOFING PERMITS, BUILDING REVIEW |
| COMMENTS. |
| CODE: FBC 5TH EDITION (2014). |
| |
| 1- DESCRIPTION SPECIFIED ON THE PERMIT APPLICATION IS |
| TO "REMOVE EXISTING ROOF, REPLACE WITH FIBERTITE |
| SINGLE-PLY". PRODUCT APPROVAL NOA 15-1026.08 SUBMITTED |
| IS FOR ROOF SYSTEMS OVER RECOVER DECKS. CLARIFY SCOPE |
| OF WORK. IS IT RE-ROOF OR RECOVER DECK. REVISE |
| DESCRIPTION ON PERMIT APPLICATION TO MATCH PRODUCT |
| APPROVAL SUBMITTED. SEC. 107.2.1 CITY AMENDMENTS. |
| |
| 2- NEED FASTENER PULL OUT TEST (TAS 105-11) AS REQUIRED |
| BY GENERAL LIMITATION #6 AND #7 ON LAST PAGE OF NOA |
| 15-1026.08 SUBMITTED AND BY ENGINEER DOING THE RAS 117 |
| CALCULATIONS SUBMITTED. NOTE: RAS 117 CALCULATIONS MAY |
| NEED TO BE REVISED BASED ON THE TEST RESULTS. |
| RAS 117 SEC. 1.2. |
| NOTE: PER PREVIOUS ROOFING MASTER APPROVALS , THE TEST |
| IS DONE ON AT LEAST ONE BUILDING AS A SAMPLE TO SHOW |
| THAT THE CONCRETE STRENGTH OF THESE BUILDINGS IS |
| ADEQUATE TO APPLY THE PROPOSED MECHANICAL ATTACHED ROOF |
| SYSTEMS. |
| |
| 3- NOA SUBMITTED IS MISSING THE GENERAL LIMITATION PAGE |
| 65 OF 65. NEED COMPLETE NOA, SUBMIT 3 COPIES OF THIS |
| PAGE. FAC 61G20-3.002(33). |
| |