Plan Review Notes
Plan Review Notes For Permit 17040741
Permit Number 17040741
Review Stop B
Sequence Number 1
Notes
Date Text
2017-04-24 12:04:00RESIDENTIAL MASTER FOR ROOFING PERMITS, BUILDING REVIEW
 COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- DESCRIPTION SPECIFIED ON THE PERMIT APPLICATION IS
 TO "REMOVE EXISTING ROOF, REPLACE WITH FIBERTITE
 SINGLE-PLY". PRODUCT APPROVAL NOA 15-1026.08 SUBMITTED
 IS FOR ROOF SYSTEMS OVER RECOVER DECKS. CLARIFY SCOPE
 OF WORK. IS IT RE-ROOF OR RECOVER DECK. REVISE
 DESCRIPTION ON PERMIT APPLICATION TO MATCH PRODUCT
 APPROVAL SUBMITTED. SEC. 107.2.1 CITY AMENDMENTS.
  
 2- NEED FASTENER PULL OUT TEST (TAS 105-11) AS REQUIRED
 BY GENERAL LIMITATION #6 AND #7 ON LAST PAGE OF NOA
 15-1026.08 SUBMITTED AND BY ENGINEER DOING THE RAS 117
 CALCULATIONS SUBMITTED. NOTE: RAS 117 CALCULATIONS MAY
 NEED TO BE REVISED BASED ON THE TEST RESULTS.
 RAS 117 SEC. 1.2.
 NOTE: PER PREVIOUS ROOFING MASTER APPROVALS , THE TEST
 IS DONE ON AT LEAST ONE BUILDING AS A SAMPLE TO SHOW
 THAT THE CONCRETE STRENGTH OF THESE BUILDINGS IS
 ADEQUATE TO APPLY THE PROPOSED MECHANICAL ATTACHED ROOF
 SYSTEMS.
  
 3- NOA SUBMITTED IS MISSING THE GENERAL LIMITATION PAGE
 65 OF 65. NEED COMPLETE NOA, SUBMIT 3 COPIES OF THIS
 PAGE. FAC 61G20-3.002(33).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (5612)805-6712
 [email protected]