Plan Review Notes
Plan Review Notes For Permit 17040656
Permit Number 17040656
Review Stop M
Sequence Number 1
Notes
Date Text
2017-04-21 12:41:241ST REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING CODES
 REVISION #17040656
 PERMIT #16070262
 4/21/17
  
 1) THE REVISED FLOOR PLAN INDICATES ROOM CONFIGURATION
 CHANGES AND CHANGES IN ROOM IDENTIFICATIONS (SEE FLOOR
 PLAN SUBMITTED UNDER PERMIT #16070262). PLEASE PROVIDE
 MECHANICAL PLANS SHOWING ALL REQUIRED ALTERATIONS TO
 THE EXISTING HVAC SYSTEMS TO ACCOMODATE THE NEW FLOOR
 PLAN LAYOUTS AND CHANGES OF ROOM USES.
  
 2) REFER TO SECTIONS 809.1 & 809.2 FBC-14 EXISTING
 BUILDING CODE AND PROVIDE MINIMUM VENTILATION
 CALCULATIONS FOR ALL ROOMS AND SPACES PER TABLE 403.3
 FBC-14 MECHANICAL. PROVIDE A SCHEDULE THAT INDICATES
 THE REQUIRED AND PROVIDED CFMS OF OUTDOOR AIR AND/OR
 EXHAUST AIR.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  