2017-04-15 06:07:48 | 1) INDICATE ON THE PLAN IF ANY TUNNELLING WILL BE |
| REQUIRED UNDER THE STRUCTURE TO ACCESS THE EXISTING |
| UNDERGROUND PIPE.IF SO, DETAILS AND BACKFILLING |
| PROCEDURES SHALL BE SUBMITTED THAT CLEARLY SHOW HOW THE |
| STRUCTURAL INTEGRITY OF THE CONCRETE SLAB WILL BE |
| MAINTAINED DURING EXCAVATION AND BACKFILLING. |
| STRUCTURAL FOAM IS NOT PERMITTED BELOW GROUND PER THE |
| FLORIDA BUILDING CODE, RESIDENTIAL, SECTION 318 AND THE |
| FLORIDA BUILDING CODE, BUILDING, SECTION 2603.8. |
| 2) IF THE EXISTING SLAB IS GOING TO BE CUT AND SOIL |
| REMOVED AND REPLACED, SUBMIT A SLAB REPAIR DETAIL FOR |
| REVIEW. THE SLAB DETAIL SHALL BE SIGNED AND SEALED BY A |
| DESIGN PROFESSIONAL REGISTERED IN THE STATE OF FLORIDA |
| PER FL. STATUTES 471 & 481.IF SOIL IS GOING TO BE |
| REMOVED AND REPLACED, THE REPLACED SOIL SHALL BE |
| TREATED WITH A TERMITICIDE IN ACCORDANCE WITH 2014 FBC |
| SEC.1816.1. |
| 3) SUBMIT MANUF. SPCECIFICATIONS FOR THE TANKLESS WATER |
| HEATERS. WPB AMEND TO FBC SEC. 107.2.1. |
| 4) INDICATE ON THE PLANS IF THE SHOWER VALVES ARE BEING |
| REPLACED. WPB AMEND TO FBC SEC. 107.2.1. |
| 5) THIS BUILDING HAS MULTIPE UNITS. WHAT ARE THE UNIT |
| NUMBERS WHERE THIS WORK IS BEING DONE? THE SUBMITTED |
| DRAWING APPEARS TO BE FOR 2 SEPARATE DWELLING UNITS. IF |
| SO, THERE IS A WATER CLOSET AND SHOWER MISSING ON THE |
| SANITARY RISER ON THE FIRST FLOOR AND A SHOWER IS |
| MISSING ON THE FIRST FLOOR WATER RISER. CLARIFY. |
| 6) SUBMIT DETAILS AS TO HOW THE PIPE PENETRATIONS |
| THROUGH THE FLOOR WILL BE FIRE SAFED TO ENSURE THE FIRE |
| RATING OF THE FLOOR ( IF RATED). INDICATE IF THE FLOOR |
| BETWEEN THE UNITS IS FIRE RATED AND THE FIRE RATING OF |
| THE FLOOR. WPB AMEND. TO FBC SEC. 107.2.1, 2014 FBC |
| SEC.714. |
| 7) INDICATE THE EXTENT OF WALL REMOVAL THAT WILL BE |
| ASSOCIATED WITH THIS REPAIR AND HOW THIS WORK WILL BE |
| REPLACED.WPB AMEND TO FBC SEC. 107.2.1. |
| 8) SUBMIT A FLOOR PLAN SHOWING WHERE THE WORK WILL BE |
| DONE IN THE UNITS.WPB AMEND TO FBC SEC. 107.2.1. |
| 9) HOW IS THE INTEGRITY OF THE EXISTING UNDERGROUND |
| BUILDING DRAIN LINE AND SEWER BEING DETERMINED AS BEING |
| IN GOOD WORKING CONDITION? IF THE INTERIOR DRAIN PIPING |
| NEEDS TO BE REPLACED THE EXISTING UNDERGROUND MAY ALSO |
| NEED TO BE REPLACED. CLARIFY. |
| 10) AS DRAWN, THE SANITARY RISER SHOWS A KITCHEN SINK |
| AND WASHING MACHINE ON A WET VENT WHICH IS NOT |
| PERMITTED PER 2014 FBC-PLUMBING SEC.912.1. ONLY |
| FIXTURES IN THE BATHROOM GROUPMAY DISCHARGE INTO A WET |
| VENT. |
| 11) AS DRAWN, THE SHOWER FOR THE 2ND FLOOR IS NOT |
| VENTED. THE SHOWER FIXTURE DRAIN SHALL CONNECT TO THE |
| STACK OR BE INDIVIDUALLY VENTED. 2014 FBC-PLUMBING |
| SEC.901.2. |
| 12) CLEANOUTS ARE REQUIRED AT THE BASE OF THE STACKS. |
| FBC-PLUMBING SEC. 708.3.4. |
| |