2017-06-01 08:35:35 | 2014 FBC- BUILDING PLAN REVIEW BUILDING |
| W. P. B. PERMIT: 17040620 |
| ADD: 780 S. SAPODILLA AVE. SUITE # 214 |
| CONT: LOWES HOME CENTERS |
| TEL: 561-721-5611 |
| E-MAIL: [email protected] |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 4 X FEE HAS BEEN ADDED TO PERMIT!!!!!!! |
| ************ 4X FEE NOTICE!!!!! FLORIDA STATUTE |
| 553.80(2)(B) ************* WITH RESPECT TO EVALUATION |
| OF DESIGN PROFESSIONALS? DOCUMENTS, IF A LOCAL |
| GOVERNMENT FINDS IT NECESSARY, IN ORDER TO ENFORCE |
| COMPLIANCE WITH THE FLORIDA BUILDING CODE AND ISSUE A |
| PERMIT, TO REJECT DESIGN DOCUMENTS REQUIRED BY THE CODE |
| THREE OR MORE TIMES FOR FAILURE TO CORRECT A CODE |
| VIOLATION SPECIFICALLY AND CONTINUOUSLY NOTED IN EACH |
| REJECTION, INCLUDING, BUT NOT LIMITED TO, EGRESS, FIRE |
| PROTECTION, STRUCTURAL STABILITY, ENERGY, |
| ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, |
| MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER |
| REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING |
| COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL |
| GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH |
| REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, |
| A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE |
| PERMIT FEE ATTRIBUTED TO PLANS REVIEW. |
| |
| 4TH REVIEW |
| DATE: THURS. JUNE 01/ 2017 |
| ACTION: DENIED |
| |
| THIS REVIEW A SALES BROCHURE FOR SMARTCORE ENGINEERED |
| LUXURY FLOORS WAS SUBMITTED. PLEASE SHOW COMPLIANCE |
| WITH: |
| BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B |
| 2014) |
| FOR TILE, STONE, MARBLE, WOOD FLOORING AND VINYL |
| FLOORING ALL NEED TO HAVE HAD THE SOUND UNDERLAYMENT |
| TESTED FLOOR ASSEMBLIES TO THE FOLLOWING STANDARDS AND |
| MEET THE QUALIFICATIONS LISTED UNDER EACH OF THE |
| STANDARDS FOR A 6 INCH CONCRETE FLOOR ASSEMBLY/ NO |
| DROPPED CEILING: |
| PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH: |
| |
| 1A) 4TH REQUEST. FBC-B 2014 1207.3 STRUCTURE-BORNE |
| SOUND. FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS |
| OR BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| |
| 1B) 4TH REQUEST. FBC-B 2014 1207.2 AIR-BORNE SOUND. |
| WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| E 90. |
| |
| 1C) 4TH REQUEST. FLAME SPREAD- FBC-B 2014 603.1. |
| EXCEPTION 2. INSULATION INSTALLED BETWEEN A FINISHED |
| FLOOR AND SOLID DECKING WITHOUT INTERVENING AIRSPACE |
| SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT |
| MORE THAN 200. |
| |
| FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| |