Date |
Text |
2017-05-04 14:09:14 | 2014 FBC- BUILDING PLAN REVIEW BUILDING |
| W. P. B. PERMIT: 17040620 |
| ADD: 780 S. SAPODILLA AVE. SUITE # 214 |
| CONT: LOWES HOME CENTERS |
| TEL: 561-721-5611 |
| E-MAIL: [email protected] |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| |
| ************ 4X FEE NOTICE!!!!! FLORIDA STATUTE |
| 553.80(2)(B) ************* WITH RESPECT TO EVALUATION |
| OF DESIGN PROFESSIONALS? DOCUMENTS, IF A LOCAL |
| GOVERNMENT FINDS IT NECESSARY, IN ORDER TO ENFORCE |
| COMPLIANCE WITH THE FLORIDA BUILDING CODE AND ISSUE A |
| PERMIT, TO REJECT DESIGN DOCUMENTS REQUIRED BY THE CODE |
| THREE OR MORE TIMES FOR FAILURE TO CORRECT A CODE |
| VIOLATION SPECIFICALLY AND CONTINUOUSLY NOTED IN EACH |
| REJECTION, INCLUDING, BUT NOT LIMITED TO, EGRESS, FIRE |
| PROTECTION, STRUCTURAL STABILITY, ENERGY, |
| ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, |
| MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER |
| REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING |
| COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL |
| GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH |
| REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, |
| A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE |
| PERMIT FEE ATTRIBUTED TO PLANS REVIEW. |
| |
| 2ND REVIEW |
| DATE: THURS. MAY 04/ 2017 |
| ACTION: DENIED |
| |
| THE SUBMITTED TEST REPORTS FOR FLOOR SOUND INSULATION |
| SELITBLOCK 2 TEST ASTM E 492-09 & ASTM E 90 BOTH ARE |
| FOR DROPPED CEILINGS WITH INSULATION, NOT CODE |
| COMPLIANT, THAT IS NOT HOW SOUTH FLORIDA BUILDS |
| HIGHRISES. |
| NO FLAME SPREAD TESTING SUBMITTED. |
| |
| BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B |
| 2014) |
| FOR TILE, STONE, MARBLE AND WOOD FLOORING ALL NEED TO |
| HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR ASSEMBLIES |
| TO THE FOLLOWING STANDARDS AND MEET THE QUALIFICATIONS |
| LISTED UNDER EACH OF THE STANDARDS FOR A 6 INCH |
| CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING: |
| PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH: |
| A) FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND. |
| FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| |
| B) FBC-B 2014 1207.2 AIR-BORNE SOUND. |
| WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| E 90. |
| |
| C) FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2. |
| INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| |
| FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| |
| JAMES A. WITMER BN, PX, CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |