2017-07-26 07:41:42 | 2ND REVIEW FBC-2014 MECHANICAL | | PERMIT #17040520 | | 7/26/17 | | | | THE COMMENTS FROM THE 1ST REVIEW STILL EXISTS. I HAVE | | REPRINTED THEM BELOW. PLEASE NOTE THE SUBMITTED | | CONTRACT FROM AM-PM AC INC. INDICATES A VALUE OF | | $4950.00 FOR THE AC WORK, HOWEVER THE RESUBMITTAL | | APPLICATION IS ONLY INDICATING AN INCREASE OF $495.00. | | I AM ASSUMING THIS IS A TYPO- PLEASE CORRECT. | | | | 1ST REVIEW FBC-2014 RESIDENTIAL MECHANICAL | | PERMIT #17040520 | | 6/16/17 | | | | 1) THE PREVIOUS REVIEW OF THE PROPOSED PROJECT | | INDICATES THAT NO PLANS OR JOB VALUE WAS PROVIDED FOR | | THE MECHANICAL WORK. NOW THAT PLANS AND A MECHANICAL | | SUB-PERMIT APPLICAION HAVE BEEN SUBMITTED, THE TOTAL | | VALUE OF THE PROJECT MUST INCREASE ACCORDINGLY. PLEASE | | PROVIDE A SIGNED CONTRACT FOR THE PROPOSED AC WORK, AND | | ADJUST THE VALUE ON THE PERMIT APPLICATION- SECTION | | | | 109.3 WPB AMENDMENTS TO THE FBC. | | | | 2) THE PROPOSED PROJECT SHALL BE IN COMPLIANCE WITH | | SECTION R101.4.3 FBC-14 ENERGY CONSERVATION. REFER TO | | SECTION R101.5.1 AND SUBMIT EITHER FORM R402 OR R405 TO | | VERIFY COMPLIANCE. | | | | 3) SUBMIT THE MIAMI-DADE NOA FOR THE CONDENSER TIE-DOWN | | CLIPS, AND PLACE THE NOA NUMBER AT THE CU MOUNTING | | DETAIL ON SHEET M-1. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | | | | | |
|