Plan Review Notes
Plan Review Notes For Permit 17040520
Permit Number 17040520
Review Stop M
Sequence Number 3
Notes
Date Text
2017-07-26 07:41:422ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17040520
 7/26/17
  
 THE COMMENTS FROM THE 1ST REVIEW STILL EXISTS. I HAVE
 REPRINTED THEM BELOW. PLEASE NOTE THE SUBMITTED
 CONTRACT FROM AM-PM AC INC. INDICATES A VALUE OF
 $4950.00 FOR THE AC WORK, HOWEVER THE RESUBMITTAL
 APPLICATION IS ONLY INDICATING AN INCREASE OF $495.00.
 I AM ASSUMING THIS IS A TYPO- PLEASE CORRECT.
  
 1ST REVIEW FBC-2014 RESIDENTIAL MECHANICAL
 PERMIT #17040520
 6/16/17
  
 1) THE PREVIOUS REVIEW OF THE PROPOSED PROJECT
 INDICATES THAT NO PLANS OR JOB VALUE WAS PROVIDED FOR
 THE MECHANICAL WORK. NOW THAT PLANS AND A MECHANICAL
 SUB-PERMIT APPLICAION HAVE BEEN SUBMITTED, THE TOTAL
 VALUE OF THE PROJECT MUST INCREASE ACCORDINGLY. PLEASE
 PROVIDE A SIGNED CONTRACT FOR THE PROPOSED AC WORK, AND
 ADJUST THE VALUE ON THE PERMIT APPLICATION- SECTION
  
 109.3 WPB AMENDMENTS TO THE FBC.
  
 2) THE PROPOSED PROJECT SHALL BE IN COMPLIANCE WITH
 SECTION R101.4.3 FBC-14 ENERGY CONSERVATION. REFER TO
 SECTION R101.5.1 AND SUBMIT EITHER FORM R402 OR R405 TO
 VERIFY COMPLIANCE.
  
 3) SUBMIT THE MIAMI-DADE NOA FOR THE CONDENSER TIE-DOWN
 CLIPS, AND PLACE THE NOA NUMBER AT THE CU MOUNTING
 DETAIL ON SHEET M-1.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  