Plan Review Notes For Permit 17040520 |
Permit Number |
17040520 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-05-10 15:38:37 | NO MECHANICAL WORK IS SHOWN ON THE PLANS. NOTE UNDER | | SCOPE OF WORKS STATES THAT THE A/C EQUIPMENT AND DUCT | | WORK ARE TO BE REPLACED BY THE A/C CONTRACTOR. SUBMIT | | EQUIPMENT SIZING CALCULATIONS, AHRI CERTIFICATIONS FOR | | THE EQUIPMENT AND PLANS FOR THE DUCTWORK WITH AN | | EQUIPMENT SCHEDULE UNDER A SEPARATE PERMIT. A SEPARATE | | PERMIT, APPLICATION AND PLANS ARE REQUIRED. DO NOT | | INCLUDE THE COST OF THIS WORK IN THE MASTER PERMIT. THE | | VALUE OF THE A/C WORK WILL BE USED FOR THE SEPARATE | | MECHANICAL PERMIT. |
|