2017-04-26 09:20:34INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA RES BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 COMMENTS:
  
 1. GENERAL NOTE TO INDICATED REQUIRED SEPARATE PERMITS
 FOR LOW VOLTAGE SYSTEMS. FBC 107.3.5
 2. SHOW AN INTERSYSTEM BONDING TERMINAL AT THE SERVICE
 PER FBC RES E3609.3
 3. SHOW EXTERIOR RECEPTACLE AT FRONT ENTRANCE TO MAIN
 HOUSE PROTECTED BY GFCI DEVICE. FBC RES E3902.3
 4. SHOW A RECEPTACLE W/P GFCI PROTECTED AT THE HVAC AC
 LOCATION FOR SERVICE PER FBC RES E3901.12 HVAC OUTLET/
 MAIN HOUSE
 5. PROVIDE A NOTE PER FBC ENERGY CONSERVATION CODE TO
 INDICATE; 75% OF LAMPS TO HIGH EFFICACY LAMPS.
 6. PROVIDE A ONE-LINE RISER DIAGRAM FOR THE ELECTRICAL
 SERVICE. FBC 107.3.5
 7. MAIN CB TO BE LOCATED OUTSIDE THE DWELLING. IF
 INSIDE BACK TO BACK SERVICE CONDUCTOR LENGTH WILL BE
 LIMITED PER THE AHJ. PROVIDE A NOTE.
 8. SHOW BONDING AND GROUNDING REQUIREMENTS.
 9. FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY
 QUESTIONS OR CONCERNS.