Plan Review Notes
Plan Review Notes For Permit 17040490
Permit Number 17040490
Review Stop B
Sequence Number 1
Notes
Date Text
2017-04-13 13:29:09****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. THE DESIGN PRESSURES ON SHEET 8.5 ARE:
  
 ZONE 4: +52, -52
 ZONE 5: +52, -95.7.
  
 THE DP LIMITATION FOR THE PROPOSED DOOR IS +-65PSF. IT
 IS NOT CLEAR IF ANY OF THE DOORS PROPOSED ARE LOCATED
 IN, OR PARTIALLY LOCATED IN, ZONE 5.
  
 PROVIDE A PLAN SHOWING THE LOCATIONS OF PROPOSED DOORS,
 FEET FROM THE CORNER. IF ANY DOORS ARE PARTIALLY IN
 ZONE 5, DESIGN PRESSURE FOR THE OPENING TO BE SPECIFIED
 BY THE ENGINEER, OR SUBMIT A PRODUCT APPROVAL FOR A
 DOOR WHICH MEETS THE REQUIREMENT FOR ZONE 5.
  
  