Plan Review Notes For Permit 17040423 |
Permit Number |
17040423 |
|
Review Stop |
G |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2017-07-19 16:54:15 | 2ND REVIEW | | | | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER LL | | CITY OF WEST PALM BEACH | | DEVELOPMENT SERVICES | | BUILDING DIVISION | | 561-805-6711 | | [email protected] | | | | GAS COMMENTS: | | | | 1. THE FIRST BRANCH DOWN STREAM OF THE FIRST WATER | | HEATER HAS 2 DIFFERENT SIZES ON IT 1' AND 11/4" PLEASE | | CLARIFY. PER WPB AMEND TO FBC 107.2.1 | | | | 2. WHAT TYPE AND SIZE IS THE NEW PIPING FROM METER TO | | EXISTING PIPING GALV PIPING IS NOT ALLOWED UNDER GROUND | | . PER FBC FG 404.11 | | | | FYI A COMPLETE AND THOROUGH REVIEW CANNOT BE DONE AT | | THIS TIME. UPON RESUBMITTAL THERE MAYBE ADDITIONAL | | COMMENTS. | | | | WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES | | AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW | | COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE | | AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW. | | |
|