2017-06-16 10:40:19PROVISO
  
 TEMPERATURE LIMITING DEVICE REQUIRED AT LAVATORY'S
 WATER HEATER THERMOSTATS DO NOT COMPLY.
  
 FBC PL 416.5 TEMPERED WATER SHALL BE DELIVERED FROM
 LAVATORIES AND GROUP WASH FIXTURES LOCATED IN PUBLIC
 TOILET FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND
 VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA B125.3. FBC PL 416.5
  
 FBC PL 607.1.1 TEMPERATURE LIMITING MEANS.
 A THERMOSTAT CONTROL FOR A WATER HEATER SHALL NOT SERVE
 AS THE TEMPERATURE LIMITING MEANS FOR THE PURPOSES OF
 COMPLYING WITH THE REQUIREMENTS OF THIS CODE FOR
 MAXIMUM ALLOWABLE HOT OR TEMPERED WATER DELIVERY
 TEMPERATURE AT FIXTURES.
  