Plan Review Notes For Permit 17040410 |
Permit Number |
17040410 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-04-14 10:46:54 | 1ST REVIEW FBC-2014 MECHANICAL | | PERMIT #17040410 | | 4/14/17 | | | | 1) PLEASE IDENTIFY ALL ROOMS AND SPACES ON THE HVAC | | PLANS WHERE WORK IS BEING PERFORMED. | | | | 2) M0.1: THE DRY BULB AND WET BULB DESIGN TEMPERATURES | | LISTED ON THE PLAN ARE NOT CONSISTENT WITH THE DESIGN | | TEMPERATURES IN THE LOAD CALULATIONS, AND THE | | TEMPERATURES LISTED IN TABLE 1A ACCA MANUAL N- SECTION | | C403.2.1 FBC-14 ENERGY CONSERVATION. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|