Plan Review Notes
Plan Review Notes For Permit 17040410
Permit Number 17040410
Review Stop M
Sequence Number 1
Notes
Date Text
2017-04-14 10:46:541ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17040410
 4/14/17
  
 1) PLEASE IDENTIFY ALL ROOMS AND SPACES ON THE HVAC
 PLANS WHERE WORK IS BEING PERFORMED.
  
 2) M0.1: THE DRY BULB AND WET BULB DESIGN TEMPERATURES
 LISTED ON THE PLAN ARE NOT CONSISTENT WITH THE DESIGN
 TEMPERATURES IN THE LOAD CALULATIONS, AND THE
 TEMPERATURES LISTED IN TABLE 1A ACCA MANUAL N- SECTION
 C403.2.1 FBC-14 ENERGY CONSERVATION.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER