2017-06-02 10:00:06CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 REVIEW COMMENTS:
  
 1. PROVIDE CORRECTION FOR EXTERIOR LIGHTS. FOR DWELLING
 UNITS, ATTACHED GARAGES, AND DETACHED GARAGES WITH
 ELECTRIC POWER, AT LEAST ONE WALL SWITCH-CONTROLLED
 LIGHTING OUTLET SHALL BE INSTALLED ON THE EXTERIOR SIDE
 OF OUTDOOR ENTRANCES OR EXITS WITH GRADE LEVEL ACCESS.
 NEC 210.70(A)(2)(B), FBC RE3903.3
 2. PROVIDE CORRECTION FOR AFCI PROTECTION. ALL
 120-VOLT, SINGLE PHASE, 15 AND 20 AMPERE BRANCH
 CIRCUITS SUPPLYING OUTLETS IN DWELLING UNIT FAMILY
 ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES,
 DENS, BEDROOMS, SUNROOMS, RECREATION ROOMS, CLOSETS,
 HALLWAYS, OR SIMILAR AREAS OR ROOMS, SHALL HAVE AFCI
 PROTECTION. NEC 210.12, FBC RE3902.12
 3. PROVIDE CORRECTION FOR MASTER CLOSET LIGHTING.
 LIGHTING WITH OPEN OR PARTIALLY ENCLOSED LAMPS AND
 PENDANT LUMINAIRES OR LAMPHOLDERS SHALL NOT BE
 PERMITTED IN CLOSETS. NEC 410.16(B), FBC RE4003.12
 4. PROVIDE CORRECTION FOR LIGHT OVER JACUZZI. LIGHTING
 IN BATHTUB OR SHOWER AREAS SHALL BE SUITABLE FOR DAMP
 OR WET LOCATIONS AS REQUIRED. NEC 410.10(A), FBC
 RE4003.11
 5. PROVIDE CORRECTION FOR POWER TO JACUZZI.
 HYDROMASSAGE TUBS AND THEIR ASSOCIATED EQUIPMENT SHALL
 BE ON AN INDIVIDUAL BRANCH CIRCUIT(S) AND PROTECTED AND
 PROTECTED BY A READILY-ACCESSIBLE GFCI. NEC 680.71, FBC
 RE4209.1
 6. PROVIDE CORRECTION FOR MASTER BATH OUTLETS. A GFCI
 PROTECTED OUTLET IS REQUIRED WITHIN 36" OF EACH BASIN.
 NEC 210.52(D), FBC RE3901.6
 7. PROVIDE CORRECTION FOR KITCHEN PENINSULA. A GFCI
 PROTECTED OUTLET IS REQUIRED FOR THE COUNTER SPACE ON A
 PENINSULA. NEC 201.52(C)(3), FBC RE3901.4.3
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  