2017-06-02 10:00:06 | CODES IN EFFECT: |
| FLORIDA BUILDING CODE 2014 5TH EDITION |
| FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| EDITION |
| NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| |
| REVIEW COMMENTS: |
| |
| 1. PROVIDE CORRECTION FOR EXTERIOR LIGHTS. FOR DWELLING |
| UNITS, ATTACHED GARAGES, AND DETACHED GARAGES WITH |
| ELECTRIC POWER, AT LEAST ONE WALL SWITCH-CONTROLLED |
| LIGHTING OUTLET SHALL BE INSTALLED ON THE EXTERIOR SIDE |
| OF OUTDOOR ENTRANCES OR EXITS WITH GRADE LEVEL ACCESS. |
| NEC 210.70(A)(2)(B), FBC RE3903.3 |
| 2. PROVIDE CORRECTION FOR AFCI PROTECTION. ALL |
| 120-VOLT, SINGLE PHASE, 15 AND 20 AMPERE BRANCH |
| CIRCUITS SUPPLYING OUTLETS IN DWELLING UNIT FAMILY |
| ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, |
| DENS, BEDROOMS, SUNROOMS, RECREATION ROOMS, CLOSETS, |
| HALLWAYS, OR SIMILAR AREAS OR ROOMS, SHALL HAVE AFCI |
| PROTECTION. NEC 210.12, FBC RE3902.12 |
| 3. PROVIDE CORRECTION FOR MASTER CLOSET LIGHTING. |
| LIGHTING WITH OPEN OR PARTIALLY ENCLOSED LAMPS AND |
| PENDANT LUMINAIRES OR LAMPHOLDERS SHALL NOT BE |
| PERMITTED IN CLOSETS. NEC 410.16(B), FBC RE4003.12 |
| 4. PROVIDE CORRECTION FOR LIGHT OVER JACUZZI. LIGHTING |
| IN BATHTUB OR SHOWER AREAS SHALL BE SUITABLE FOR DAMP |
| OR WET LOCATIONS AS REQUIRED. NEC 410.10(A), FBC |
| RE4003.11 |
| 5. PROVIDE CORRECTION FOR POWER TO JACUZZI. |
| HYDROMASSAGE TUBS AND THEIR ASSOCIATED EQUIPMENT SHALL |
| BE ON AN INDIVIDUAL BRANCH CIRCUIT(S) AND PROTECTED AND |
| PROTECTED BY A READILY-ACCESSIBLE GFCI. NEC 680.71, FBC |
| RE4209.1 |
| 6. PROVIDE CORRECTION FOR MASTER BATH OUTLETS. A GFCI |
| PROTECTED OUTLET IS REQUIRED WITHIN 36" OF EACH BASIN. |
| NEC 210.52(D), FBC RE3901.6 |
| 7. PROVIDE CORRECTION FOR KITCHEN PENINSULA. A GFCI |
| PROTECTED OUTLET IS REQUIRED FOR THE COUNTER SPACE ON A |
| PENINSULA. NEC 201.52(C)(3), FBC RE3901.4.3 |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |
| SINCERELY, |
| |
| JOHN PEARSON |
| ELECTRICAL PLANS EXAMINER |