Plan Review Notes
Plan Review Notes For Permit 17040397
Permit Number 17040397
Review Stop B
Sequence Number 2
Notes
Date Text
2017-06-20 08:30:31BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 2ND REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. SQUARE FOOTAGE OF ATTACHED GARAGE STATED AS 300 SQ.
 FT. (SEE ELEVATION CERTIFCATE A9 A). THIS SHOULD BE 464
 SQ. FT.
 2. SCOPE OF WORK INCREASED TO INCLUDE THE INSTALLATION
 OF FLOOD VENTS.
 3. IF ENGINEERED VENTS ARE INSTALLED, PROVIDE DESIGN
 CERTIFIED BY A REGISTERED DESIGN PROFESSIONAL OR AN
 EVALUATION REPORT ISSUED BY THE INTERNATIONAL CODE
 COUNCIL (ICC) EVALUATION SERVICE, INC.
 4. IF NON-ENGINEERED OPENINGS ARE INSTALLED, REFER TO
 FEMA'S NON-ENGINEERED OPENING GUIDE, VOLUME 1 DATED
 JANUARY 2015.
 5. LOCATION OF PROPOSED VENTS ARE ON ONE WALL. REFER TO
 FEMA'S OPENINGS IN FOUNDATION WALLS AND WALLS OF
 ENCLOSURES TECHNICAL BULLENTIN 1 DATE AUGUST 2008. IT
 IS RECOMMENDED THAT OPENINGS BE REASONBLY DISTRIBUTED
 AROUND THE PEREMITER OF THE ENCLOSED AREA UNLESS THERE
 IS CLEAR JUSTIFICATION FOR PUTTING ALL OPENINGS ON JUST
 ONE OR TWO SIDES. THERE APPEARS TO BE AN AREA LOCATED
 ADJACENT TO THE FOYER EXTERIOR DOOR TO LOCATE AT LEAST
 ONE VENT.
 6. FINAL ELEVATION CERTIFCATE REQUIRED PRIOR TO FINAL
 INSPECTION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED AND MARK VOID.
  
  
  
  