2017-06-20 08:30:31 | BUILDING PLAN REVIEW |
| 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1 |
| ADMINISTRATION |
| |
| CHRISTOPHER S. THROOP, C.B.O. |
| PLANS EXAMINER, PX3169 |
| CONSTRUCTION SERVICES DIVISION |
| TEL: 561-805-6726 |
| FAX: 561-805-6676 |
| |
| 2ND REVIEW |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| |
| 1. SQUARE FOOTAGE OF ATTACHED GARAGE STATED AS 300 SQ. |
| FT. (SEE ELEVATION CERTIFCATE A9 A). THIS SHOULD BE 464 |
| SQ. FT. |
| 2. SCOPE OF WORK INCREASED TO INCLUDE THE INSTALLATION |
| OF FLOOD VENTS. |
| 3. IF ENGINEERED VENTS ARE INSTALLED, PROVIDE DESIGN |
| CERTIFIED BY A REGISTERED DESIGN PROFESSIONAL OR AN |
| EVALUATION REPORT ISSUED BY THE INTERNATIONAL CODE |
| COUNCIL (ICC) EVALUATION SERVICE, INC. |
| 4. IF NON-ENGINEERED OPENINGS ARE INSTALLED, REFER TO |
| FEMA'S NON-ENGINEERED OPENING GUIDE, VOLUME 1 DATED |
| JANUARY 2015. |
| 5. LOCATION OF PROPOSED VENTS ARE ON ONE WALL. REFER TO |
| FEMA'S OPENINGS IN FOUNDATION WALLS AND WALLS OF |
| ENCLOSURES TECHNICAL BULLENTIN 1 DATE AUGUST 2008. IT |
| IS RECOMMENDED THAT OPENINGS BE REASONBLY DISTRIBUTED |
| AROUND THE PEREMITER OF THE ENCLOSED AREA UNLESS THERE |
| IS CLEAR JUSTIFICATION FOR PUTTING ALL OPENINGS ON JUST |
| ONE OR TWO SIDES. THERE APPEARS TO BE AN AREA LOCATED |
| ADJACENT TO THE FOYER EXTERIOR DOOR TO LOCATE AT LEAST |
| ONE VENT. |
| 6. FINAL ELEVATION CERTIFCATE REQUIRED PRIOR TO FINAL |
| INSPECTION. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY |
| REVIEWED SHEETS DETACHED AND MARK VOID. |
| |
| |
| |
| |