2017-04-17 18:52:15RESIDENTIAL (R3) ALTERATION, BUILDING REVIEW COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- SPECIFY SIZE AND TYPE OF EXISTING WINDOWS TO BE
 REPLACED TO VERIFY COMPLIANCE WITH EGRESS REQUIREMENTS.
 SEC. 704 FBC-EXISTING BUILDING, 5TH EDITION (2014).
  
 2- SPECIFY SIZE OF EXISTING FRENCH DOORS TO BE REPLACED
 TO VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC.
 R301.1 FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 3- CLEARLY SPECIFY SIZE OF WINDOW MULLIONS TO VERIFY
 COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. R301.1
 FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 4- CLEARLY MARK WHICH ARE THE WINDOWS TO BE REPLACED.
 HIGHLIGHTED WINDOWS ON THE PLANS SUBMITTED DON'T ADD UP
 TO 23 WINDOWS AS SPECIFIED ON THE PERMIT APPLICATION.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 5- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS AND
 CONTRACTOR'S OVERHEAD AND PROFIT AS REQUIRED BY SEC.
 109.3 CITY AMENDMENTS. UPDATE VALUATION AS REQUIRED.
  