2017-04-17 17:08:311ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17040376
 4/17/17
  
 1) PROVIDE WIND LOAD ENGINEERING FOR INSTALLATION OF
 THE ROOF TOP UNIT- SECTION 301.15.
  
 2) CONTRACTOR PLANS SHALL BE DRAWN TO SCALE AND PROVIDE
 CLEAR DETAILS. THE PLANS SHALL ALSO BE SIGNED BY THE
 PERSON WHO PREPARED THE DRAWING- SECTION 107.2.1 WPB
 AMENDMENTS TO THE FBC.
  
 3) PROVIDE AN EQUIPMENT SCHEDULE ON THE PLANS THAT
 INDICATES THE MAKE AND MODEL OF THE EQUIPMENT, THE
 COOLING AND HEATING CAPACITIES, THE TOTAL SUPPLY CFMS,
 AND THE EFFICIENCY RATING.
  
 4) SUBMIT AN AHRI CERTIFICATE FOR THE SYSTEM
  
 5) PROVIDE SEPARATE LAYOUT PLANS FOR THE FIRST AND
 SECOND FLOOR THAT IDENTIFY THE ROOMS, DUCT SIZES,
 SUPPLY DIFFUSER AND RETURN GRILL SIZES, AND CFMS AT
 EACH LOCATION.
  
 6) INDICATE THE TYPE OF DUCTWORK TO BE INSTALLED AND
 PROVIDE SUPPORT AND CONNECTION DETAILS ON THE PLAN PER
 SMACNA STANDARDS.
  
 7) PROVIDE AN AIR DEVICE SCHEDULE ON THE PLANS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER