Plan Review Notes
Plan Review Notes For Permit 17040313
Permit Number 17040313
Review Stop B
Sequence Number 2
Notes
Date Text
2017-04-12 09:07:33RE-ROOF SECOND BUILDING REVIEW CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 1- FLORIDA PRODUCT APPROVAL FL2533-R17 SUBMITTED: THE
 DESIGN PRESSURES FOR THE SELECTED ASSEMBLY W-57 ARE
 -75.0. THE DESIGN PRESSURES FOR THE CORNER AREAS OF
 THIS BUILDING ARE HIGHER. NEED TO SELECT ANOTHER
 ASSEMBLY THAT MEETS THE DESIGN PRESSURES FOR ALL ROOF
 ZONES OR NEED TO PROVIDE SIGNED AND SEALED RAS 117
 CALCULATIONS AS REQUIRED BY NOTE #8 ON PAGE 2 OF 57 TO
 MEET THE DESIGN PRESSURES FOR THE CORNER AREAS. NEED
 THE CALCULATIONS TO COMPLY WITH THE DESIGN PRESSURES
 REQUIRED BY SEC. 1609.1 FBC, 5TH EDITION (2014).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]