Plan Review Notes For Permit 17040313 |
Permit Number |
17040313 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-04-10 17:57:18 | RE-ROOF BUILDING REVIEW COMMENTS. | | CODE: FBC 5TH EDITION (2014). | | | | 1- FLORIDA PRODUCT APPROVAL FL2533-R11 SUBMITTED IS TOO | | OLD. THIS PRODUCT APPROVAL HAVE BEING REVISED SEVERAL | | TIMES AND THE SELECTED ASSEMBLY W-52 IS NO LONGER THE | | SAME. THE CURRENT FLORIDA PRODUCT APPROVAL IS | | FL2533-R-17. PROVIDE CURRENT FLORIDA PRODUCT APPROVAL | | AND MARK PROPOSED ASSEMBLY TO BE INSTALLED TO VERIFY | | COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. 1609.1 | | FBC, 5TH EDITION (2014). | | | | 2- THIS IS A VERY LARGE BUILDING. THERE ARE SEVERAL | | FLAT ROOFS IN THIS BUILDING. PROVIDE SKETCH SHOWING | | LOCATION AND DIMENSIONS OF THE FLAT AREA TO BE | | RE-ROOFED. SEC. 107.2.1 AND SEC. 109.3 CITY AMENDMENTS | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | (561)805-6712 | | [email protected] |
|