2017-04-10 15:46:57RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- TU-PLUS FLORIDA PRODUCT APPROVAL FL5259-R25
 SUBMITTED: PLEASE MARK WHICH SYSTEM FROM SEC. 5.6.4 IS
 GOING TO BE APPLIED TO MEET THE ROOF DESIGN PRESSURES.
 NEED THIS INFORMATION TO VERIFY COMPLIANCE WITH-THE
 DESIGN PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL., 5TH
 EDITION (2014). NOTE: YOU MAY USE ONE SYSTEM FOR THE
 FIELD AND PERIMETER AREAS AND ANOTHER SYSTEM FOR THE
 CORNER AREAS. SEE SEC. 5.6.4.1 AND SYSTEM SEC. 5.6.4.2
 FOR THE CORNER AREAS. OR, YOU CAN USE THE SECOND SYSTEM
 FOR THE ENTIRE ROOF.
  