2017-04-21 13:11:37BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE STRUCTURAL DETAIL FOR CONCRETE PAD.
 2.1603.1.7 FLOOD DESIGN DATA.
 FOR BUILDINGS LOCATED IN WHOLE OR IN PART IN FLOOD
 HAZARD AREAS AS ESTABLISHED IN SECTION 1612.3, THE
 DOCUMENTATION PERTAINING TO DESIGN, IF REQUIRED IN
 SECTION 1612.5, SHALL BE INCLUDED AND THE FOLLOWING
 INFORMATION, REFERENCED TO THE DATUM ON THE COMMUNITY?S
 FLOOD INSURANCE RATE MAP (FIRM), SHALL BE SHOWN,
 REGARDLESS OF WHETHER FLOOD LOADS GOVERN THE DESIGN OF
 THE BUILDING:
  
 2.2. CONSTRUCTION DOCUMENTS SHALL INCLUDE A STATEMENT
 THAT THE BUILDING IS DESIGNED IN ACCORDANCE WITH ASCE
 24, INCLUDING THAT THE PILE OR COLUMN FOUNDATION AND
 BUILDING OR STRUCTURE TO BE ATTACHED THERETO IS
 DESIGNED TO BE ANCHORED TO RESIST FLOTATION, COLLAPSE
 AND LATERAL MOVEMENT DUE TO THE EFFECTS OF WIND AND
 FLOOD LOADS ACTING SIMULTANEOUSLY ON ALL BUILDING
 COMPONENTS, AND OTHER LOAD REQUIREMENTS OF CHAPTER 16.
  