2017-08-30 09:51:25 | 1) PROVIDE A FIRESTOPPING DETAIL FOR PVC PIPE THROUGH |
| FIRE RATED WALLS. THE PIPE FIRESTOPPING DETAILS ON |
| SHEET A0.05 ARE ONLY FOR FERRROUS AND NON-FERROUS PIPE. |
| 2014 FBC SEC. 714.3.1. |
| 2) THE WALL FINISH AROUND THE MOP/SERVICE SINK SHALL |
| COMPLY WITH THE 2015 FBC SEC.1210.2.2. |
| 3) SHT. A4.23 - THE DOORS ON THE AMBULATORY ACCESSIBLE |
| STALLS IN THE MEN'S AND WOMEN'S RESTROOMS SHALL NOT |
| SWING INTO THE MINIMUM REQUIRED COMPARTMENT AREA. 2014 |
| FBC-ACCESS. SEC. 604.8.2.2. |
| 4) SHT.A4.23 - DETAIL #1 - ENLARGED TOILET ROOM - THE |
| HANDICAPPED ACCESSIBLE TOILET STALLS SHOW THE WATER |
| CLOSETS AT 1'-7" FROM THE ADJACENT WALL TO THE |
| CENTERLINE OF THE WATER CLOSET. THE WATER CLOSETS SHALL |
| BE LOCATED 16 INCHES MINIMUM TO 18 INCHES MAXIMUM TO |
| THE SIDE WALL. |
| 2014 FBC-ACCESS. SEC.604.2. |
| 5) SHT. A4.23 - DETAIL #3 - NOTE ON THE PLAN THAT THE |
| SHOWER CONTROLS SHALL BE LOCATED 15 INCHES MAXIMUM FRON |
| THE CENTERLINE OF THE SEAT TOWARD THE SHOWER |
| OPENING.2014 FBC-ACCESS SEC.608.5.1. |
| 6) A FIXED SHOWER HEAD LOCATED 48 INCHES MAXIMUM ABOVE |
| THE SHOWER FINISH FLOOR SHALL BE PERMITTED INSTEAD OF A |
| HAND-HELD SPRAY UNIT PER 2014 FBC-ACCESS SEC.608.6. |
| SHOW COMPLIANCE ON THE PLANS OR SUPPLY A SHOWER SPRAY |
| UNIT IN COMPLIANCE WITH 2014 FBC-ACCESS. SEC. 608.6. |
| 7) SHT. P0.1 - WATER HEATER DETAIL - DELETE THE |
| REFERENCE TO THE RELIEF LINE BEING PIPED TO THE |
| EXTERIOR AND CHANGE THE CODE TO 2014 FBC, NOT 2010. |
| 8) SHT. P5.1 - SANITARY RISER - WHERE DOES THE VENT FOR |
| THE THE DRINKING FOUNTAIN/SK-1 / MOP SINK TERMINATE? |
| WHERE IS THE VENT THROUGH THE ROOF? THIS ALSO OCCURS ON |
| THE VENT FOR THE GANG TOILETS. CLARIFY. |
| 9) SUBMIT AN EXPANDED SANITARY AND WATER RISER FOR |
| REVIEW. A COMPREHENSIVE REVIEW CANNOT BE DONE AS THE |
| DRAWING IS TOO CCOMPRESSED. WPB AMEND. TO FBC SEC. |
| 107.2.1. |
| 10) SHT.P5.1 - THE SANITARY RISER SHOWS 6 LAVATORIES IN |
| A ROW IN THE MEN'S RESTROOM AND THE FLOOR PLAN ON P |
| 2.2.1 SHOWS 5 LAVATORIES. CLARIFY. 11) |
| 11) THE SANITARY RISER FOR THE MEN''S & WOMEN'S |
| RESTROOM DOES NOT COMPLY WITH 2014 FBC-PLUMBING |
| SEC.914.1, 914.2 FOR A CIRCUIT VENT. CLARIFY. |
| 12) SIZE THE TYPICAL VENT STACK FFOR THE LAVATORIES ON |
| THE SANITARY RISER.COMPLY WITH 2014 FBC-PLUMBING |
| SEC.906.1 & TABLE 906.1. |
| |
| TIM LARGE |
| CHIEF PLUMBING INSPECTOR |
| PLUMBING PLAN REVIEW |
| 561-805-6692 |
| [email protected] |
| |
| |