Plan Review Notes
Plan Review Notes For Permit 17040199
Permit Number 17040199
Review Stop P
Sequence Number 4
Notes
Date Text
2017-08-30 09:51:251) PROVIDE A FIRESTOPPING DETAIL FOR PVC PIPE THROUGH
 FIRE RATED WALLS. THE PIPE FIRESTOPPING DETAILS ON
 SHEET A0.05 ARE ONLY FOR FERRROUS AND NON-FERROUS PIPE.
 2014 FBC SEC. 714.3.1.
 2) THE WALL FINISH AROUND THE MOP/SERVICE SINK SHALL
 COMPLY WITH THE 2015 FBC SEC.1210.2.2.
 3) SHT. A4.23 - THE DOORS ON THE AMBULATORY ACCESSIBLE
 STALLS IN THE MEN'S AND WOMEN'S RESTROOMS SHALL NOT
 SWING INTO THE MINIMUM REQUIRED COMPARTMENT AREA. 2014
 FBC-ACCESS. SEC. 604.8.2.2.
 4) SHT.A4.23 - DETAIL #1 - ENLARGED TOILET ROOM - THE
 HANDICAPPED ACCESSIBLE TOILET STALLS SHOW THE WATER
 CLOSETS AT 1'-7" FROM THE ADJACENT WALL TO THE
 CENTERLINE OF THE WATER CLOSET. THE WATER CLOSETS SHALL
 BE LOCATED 16 INCHES MINIMUM TO 18 INCHES MAXIMUM TO
 THE SIDE WALL.
 2014 FBC-ACCESS. SEC.604.2.
 5) SHT. A4.23 - DETAIL #3 - NOTE ON THE PLAN THAT THE
 SHOWER CONTROLS SHALL BE LOCATED 15 INCHES MAXIMUM FRON
 THE CENTERLINE OF THE SEAT TOWARD THE SHOWER
 OPENING.2014 FBC-ACCESS SEC.608.5.1.
 6) A FIXED SHOWER HEAD LOCATED 48 INCHES MAXIMUM ABOVE
 THE SHOWER FINISH FLOOR SHALL BE PERMITTED INSTEAD OF A
 HAND-HELD SPRAY UNIT PER 2014 FBC-ACCESS SEC.608.6.
 SHOW COMPLIANCE ON THE PLANS OR SUPPLY A SHOWER SPRAY
 UNIT IN COMPLIANCE WITH 2014 FBC-ACCESS. SEC. 608.6.
 7) SHT. P0.1 - WATER HEATER DETAIL - DELETE THE
 REFERENCE TO THE RELIEF LINE BEING PIPED TO THE
 EXTERIOR AND CHANGE THE CODE TO 2014 FBC, NOT 2010.
 8) SHT. P5.1 - SANITARY RISER - WHERE DOES THE VENT FOR
 THE THE DRINKING FOUNTAIN/SK-1 / MOP SINK TERMINATE?
 WHERE IS THE VENT THROUGH THE ROOF? THIS ALSO OCCURS ON
 THE VENT FOR THE GANG TOILETS. CLARIFY.
 9) SUBMIT AN EXPANDED SANITARY AND WATER RISER FOR
 REVIEW. A COMPREHENSIVE REVIEW CANNOT BE DONE AS THE
 DRAWING IS TOO CCOMPRESSED. WPB AMEND. TO FBC SEC.
 107.2.1.
 10) SHT.P5.1 - THE SANITARY RISER SHOWS 6 LAVATORIES IN
 A ROW IN THE MEN'S RESTROOM AND THE FLOOR PLAN ON P
 2.2.1 SHOWS 5 LAVATORIES. CLARIFY. 11)
 11) THE SANITARY RISER FOR THE MEN''S & WOMEN'S
 RESTROOM DOES NOT COMPLY WITH 2014 FBC-PLUMBING
 SEC.914.1, 914.2 FOR A CIRCUIT VENT. CLARIFY.
 12) SIZE THE TYPICAL VENT STACK FFOR THE LAVATORIES ON
 THE SANITARY RISER.COMPLY WITH 2014 FBC-PLUMBING
 SEC.906.1 & TABLE 906.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  