Plan Review Notes
Plan Review Notes For Permit 17040199
Permit Number 17040199
Review Stop P
Sequence Number 3
Notes
Date Text
2017-07-24 12:41:253RD REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
  
 3RD REQUEST PREVIOUS COMMENT NOT COMPLIED 2. PER FBC
 ACC 213.3.1 AT LEAST ONE OF THE TOILET COMPARTMENTS IN
 EACH BATHROOM SHALL BE AN AMBULATORY STALL PER FBC
 604.8.2 ( YOU ARE MISSING THE GRAB BARS)
 213.3.1 TOILET COMPARTMENTS.
 WHERE TOILET COMPARTMENTS ARE PROVIDED, AT LEAST ONE
 TOILET COMPARTMENT SHALL COMPLY WITH 604.8.1. IN
 ADDITION TO THE COMPARTMENT REQUIRED TO COMPLY WITH
 604.8.1, AT LEAST ONE COMPARTMENT SHALL COMPLY WITH
 604.8.2 WHERE SIX OR MORE TOILET COMPARTMENTS ARE
 PROVIDED, OR WHERE THE COMBINATION OF URINALS AND WATER
 CLOSETS TOTALS SIX OR MORE FIXTURES.
 THIS CODE REQUIREMENT IS FOR THE FIXTURES PROVIDED NOT
 FIXTURES REQUIRED.
  
 NEW COMMENT
 1. SHT.4.23 DETAIL #1 THE DIMENSION FOR THE DEPTH OF
 THE TRANSFER SHOWER IS AN EXACT MEASUREMENT NOT A MIN
 PLEASE CLARIFY. PER FBC ACC 608.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  