2017-07-24 08:47:04 | CODES IN EFFECT: |
| FLORIDA BUILDING CODE 2014 5TH EDITION |
| FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| EDITION |
| NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| |
| BASED ON REVISION PROVIDED, NEW ELECTRICAL REVIEW |
| COMMENTS: |
| |
| 1. PANEL L1A SHOWS A 225 AMP MAIN BREAKER, WHICH |
| EXCEEDS THE PERMITTED RATING PER CODE. PROVIDE |
| CORRECTION. NEC TABLE 450.3(B) |
| 2. PROVIDE PANEL SCHEDULE FOR BYPASS PANEL AND PANEL |
| UPS. NEC 215.5, 408.4, 408.30; FBC 107.2.1 |
| 3. PROVIDE SHORT CIRCUIT CALCULATIONS FOR SERVICES ON |
| 1ST AND 7TH FLOOR TO CONFIRM AIC RATINGS OF PANELS IS |
| SUFFICIENT, INCLUDE THE TRANSFORMER SECONDARY |
| CALCULATION OF 75KVA TRANSFORMER FEEDING PANEL IT. |
| PROVIDE NOTE THAT SERVICE EQUIPMENT SHALL BE MARKED PER |
| NEC 110.24. NEC 110.9, 110.10, 110.24 |
| 4. LOAD FOR PANEL H EXCEEDS THE OVERCURRENT PROTECTION |
| AND AMPACITY OF WIRE STATED ON PLAN. PROVIDE |
| CORRECTION. NEC 215.2, 215.3, 310.15(B)(16), 240.4 |
| 5. PROVIDE LIGHTING CONTROL PANEL DETAIL, INCLUDE ALL |
| CIRCUITS CONTROLLED BY PANEL. FBC 107.2.1, C405.2 |
| 6. SHEET E3.2 AND E3.2.1, KEY NOTE #2, STATES THERE IS |
| A DETAIL OF TIME CLOCK CONTACTOR C-1 ON SHEET E5.1. |
| THIS DETAIL IS NOT ON ANY OF THE SHEETS. PROVIDE DETAIL |
| OF ALL CONTACTOR CONTROL PANELS USED FOR RECEPTACLE |
| CONTROL. REVIEWER NOTED SEVERAL CIRCUITS FROM PANELS |
| NOT ON ANY OF THE CONTACTOR DETAILS PROVIDED. FBC |
| 107.2.1, C405.7.1 |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |