Plan Review Notes For Permit 17040199 |
Permit Number |
17040199 |
|
Review Stop |
FIRE |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2017-06-05 16:51:13 | 2ND REVIEW | | | | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) COMPLIED | | | | | | 2) COMPLIED | | | | | | | | 3) DENIED - SHEET A 1.11 AND SHEETS A 5.11 & 5.12, WERE | | NOT ATTACHED TO THE RE-SUBMITTED PACKET. | | | | HOWEVER, ON REVIEW OF THE VOIDED SHEET A 5.11 THAT UL | | LISTING WAS FOUND. | | | | PLEASE ATTACHED ALL APPLICABLE SHEETS TO THE | | RESUBMITTAL. | | | | | | | | | | 4) DENIED - THE NOTE COMMENT REMIANS. THIS NOTE | | COMMENTS NEEDS TO BE REVIEWED AS THERE ARE NO FA | | DEVICES OF THE ELECTRICAL SHEETS. | | | | FA DEVICES SHALL BE INSTALLED PER NFPA 72 UNDER | | SEPARATE SHOP DRAWINGS. | | | | | | PLEASE CORRECT.. | | | | | | | | 5) DENIED - THE "NOT" SHALL BE PLACED AFTER THE SHALL. | | CARD READERS SHALL "NOT" DELAY OR INTERFERE WITH ANY | | EXIT DOOR AND SHALL COMPLY WITH NFPA 101, CHAPTER 7, | | MEANS OF EGRESS AND SHALL BE INSTALLED UNDER SEPARATE | | SHOP DRAWINGS. | | | | PLEASE CORRECT. | | | | | | | | 6) COMPLIED | | | | | | | | 7) COMPLIED | | | | | | | | 8) COMMENT REMAINS - WHEN RESUBMITTING, PLEASE PROVIDE | | PLAN SHEET REVISION CLOUDS OR NUMBERED NARRATIVE | | RESPONSES TO THE ABOVE. | | | | | | | | 9) COMMENT REMAINS - ADDITIONAL COMMENTS MAY BE | | PROVIDED ON THE RE-SUBMITTAL OF THE ABOVE. | | | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] |
|