2017-06-08 10:48:04 | 2014 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 17040199 |
| ADD: 1515 N. FLAGLER DR. SUITE 100 & 700 |
| CONT: LB DEVELOPMENT & ENGINEERING |
| TEL: 954-881-5693 |
| E-MAIL: [email protected] |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 2ND REVIEW |
| DATE: THURS. JUNE 08/ 2017 |
| ACTION: DENIED |
| |
| PLEASE READ!!!!!! THE RESUBMITTED NEW SET OF PLANS WAS |
| NOT COLLATED WITH THE OLD PLAN SETS. THE NEW PLAN SETS |
| WERE NOT COMPLETE SET OF PLANS!!!!! MISSING PLANS ONLY |
| FOR ARCHITECTURE ARE: |
| |
| A0.04-A0.12 MISSING |
| A0.14 MISSING |
| A0.17-A4.21 MISSING |
| A4.25-A5.51 MISSING |
| |
| A COMPLETE PLAN REVIEW CAN NOT BE COMPLETED UNTIL THE |
| CONTRACTOR COLLATES THE PLANS! |
| |
| 1) SHEET A0.13 THE DOOR SCHEDULE SHOWS THE ENTRY DOOR # |
| 18 WITH HARDWARE GROUP # 1 VANDAL ENTRANCE LOCK NOT |
| PANIC HARDWARE, THIS IS ALLOWED, CODE COMPLIANT ON THE |
| MAIN ENTRY DOOR BY EXCEPTION . 1008.1.9.3, ITEM 2. IF: |
| 2. IN BUILDINGS IN OCCUPANCY GROUP A HAVING AN OCCUPANT |
| LOAD OF 300 OR LESS, GROUPS B, F, M AND S, AND IN |
| PLACES OF RELIGIOUS WORSHIP, THE MAIN EXTERIOR DOOR OR |
| DOORS ARE PERMITTED TO BE EQUIPPED WITH KEY-OPERATED |
| LOCKING DEVICES FROM THE EGRESS SIDE PROVIDED: |
| 2.1. THE LOCKING DEVICE IS READILY DISTINGUISHABLE AS |
| LOCKED; |
| 2.2. A READILY VISIBLE DURABLE SIGN IS POSTED ON THE |
| EGRESS SIDE ON OR ADJACENT TO THE DOOR STATING: THIS |
| DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. THE |
| SIGN SHALL BE IN LETTERS 1 INCH (25 MM) HIGH ON A |
| CONTRASTING BACKGROUND; AND |
| 2.3. THE USE OF THE KEY-OPERATED LOCKING DEVICE IS |
| REVOKABLE BY THE BUILDING OFFICIAL FOR DUE CAUSE. |
| |
| 2) SHEET A0.13 THE DOOR SCHEDULE SHOWS THE DOOR TO THE |
| TRAINING ROOM, DOOR # 20 ALSO WITH A VANDAL ENTRY LOCK. |
| THIS DOOR SHOULD HAVE PANIC HARDWARE IN ACCORDANCE WITH |
| 1008.1.10. |
| |
| 3) THE DESIGNER OF RECORD INDICATES 1 HOUR FIRE RATED |
| WALLS BETWEEN THE TENANT SPACE AND COMMON AREAS AS WELL |
| AS THE TRAINING ROOM 707. PLEASE REVIEW THE MECHANICAL |
| COMMENT # 5 MISSING FIRE DAMPERS IN FIRE RATED WALLS |
| AND COMPLIANCE WITH 2014 FBC-B 714.1.1 DUCTS AND AIR |
| TRANSFER OPENINGS. |
| PENETRATIONS OF FIRE-RESISTANCE-RATED WALLS BY DUCTS |
| THAT ARE NOT PROTECTED WITH DAMPERS SHALL COMPLY WITH |
| SECTIONS 714.2 THROUGH 714.3.3. MISSING FIRE DAMPERS |
| SEE M2.2.1. 10X8 O/A DUCT PENETRATING THE TRAINING/ |
| CORRIDOR WALL, 16X12 O/A DUCT PENETRATING THE TRAINING |
| ROOM/ CORRIDOR WALL, TRAINING ROOM/ VESTIBULE/ MENS |
| RESTROOM AND THE 8X8 SUPPLY DUCT PENETRATING THE COPY |
| ROOM/ ELEVATOR LOBBY WALL. |
| |
| 4) THE NEW OUTSIDE AIR DUCT WILL REQUIRE AN OUTSIDE AIR |
| LOUVER ON THE EXTERIOR OF THE BUILDING. PLEASE PROVIDE |
| COMPLIANCE WITH: 1609.6.4.4.1 COMPONENTS & CLADDING. |
| FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE |
| CODE 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31) |
| SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT |
| WILL REQUIRE PRODUCT APPROVALS: |
| (31(C) PANEL WALLS: WALL LOUVERS |
| |
| 5) FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP DRAWINGS ETC.. |
| 6) THE RESTROOM DETAIL 1/ A4.23 IN BOTH RESTROOMS SHOWS |
| 6 OR MORE WATER CLOSETS AND OR COMBINATION OF WATER |
| CLOSETS AND URINALS THEN COMPLIANCE WITH SECTION |
| 213.3.1 OF THE 2014 ACCESSIBILITY CODE IS REQUIRED. |
| ALSO SEE: |
| 604.8.2 AMBULATORY ACCESSIBLE COMPARTMENTS. AMBULATORY |
| ACCESSIBLE COMPARTMENTS SHALL COMPLY WITH 604.8.2. |
| 604.8.2.2 DOORS. TOILET COMPARTMENT DOORS, INCLUDING |
| DOOR HARDWARE, SHALL COMPLY WITH 404, EXCEPT THAT IF |
| THE APPROACH IS TO THE LATCH SIDE OF THE COMPARTMENT |
| DOOR, CLEARANCE BETWEEN THE DOOR SIDE OF THE |
| COMPARTMENT AND ANY OBSTRUCTION SHALL BE 42 INCHES |
| (1065 MM) MINIMUM. THE DOOR SHALL BE SELF-CLOSING. A |
| DOOR PULL COMPLYING WITH 404.2.7 SHALL BE PLACED ON |
| BOTH SIDES OF THE DOOR NEAR THE LATCH. TOILET |
| COMPARTMENT DOORS SHALL NOT SWING INTO THE MINIMUM |
| REQUIRED COMPARTMENT AREA. |
| |
| 604.8.2.3 GRAB BARS. GRAB BARS SHALL COMPLY WITH 609. A |
| SIDE-WALL GRAB BAR COMPLYING WITH 604.5.1 SHALL BE |
| PROVIDED ON BOTH SIDES OF THE COMPARTMENT. |
| |
| 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |