2017-04-11 09:14:161ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17040199
 4/11/17
  
 1) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE
 NEW HEAT PUMPS- SECTION C403.2.1 FBC-14 ENERGY
 CONSERVATION
  
 2) PROVIDE EQUIPMENT SCHEDULES FOR EF-1 & 2.
  
 3) PROVIDE EXHAUST VENTILATION CALCULATIONS FOR THE
 WOMEN'S AND MEN'S RESTROOMS.
  
 4) M6.2: PLEASE CLARIFY HOW THE O/A UNITS WERE SIZED
 AND FOR WHAT AREAS THEY ARE SERVING.
  
 5) M2.21: MISSING FIRE DAMPERS- A) 10X8 O/A DUCT
 PENETRATING THE TRAINING/CORRIDOR WALL. B) 16X12 O/A
 DUCT PENETRATING THE TRAINING/CORRIDOR WALL, AND THE
 TRAINING/VESTIBULE/MEN'S RESTROOM WALLS. C) 8X8 SUPPLY
 DUCT PENETRATING THE COPY ROOM/ELEVATOR LOBBY WALL.
  
 6) SUBMIT AN APPROVED FL. PRODUCT APPROVAL AND/OR
 MIAMI-DADE NOA FOR THE LOUVERS.
  