Plan Review Notes For Permit 17040199 |
Permit Number |
17040199 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-04-11 09:14:16 | 1ST REVIEW FBC-2014 MECHANICAL | | PERMIT #17040199 | | 4/11/17 | | | | 1) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE | | NEW HEAT PUMPS- SECTION C403.2.1 FBC-14 ENERGY | | CONSERVATION | | | | 2) PROVIDE EQUIPMENT SCHEDULES FOR EF-1 & 2. | | | | 3) PROVIDE EXHAUST VENTILATION CALCULATIONS FOR THE | | WOMEN'S AND MEN'S RESTROOMS. | | | | 4) M6.2: PLEASE CLARIFY HOW THE O/A UNITS WERE SIZED | | AND FOR WHAT AREAS THEY ARE SERVING. | | | | 5) M2.21: MISSING FIRE DAMPERS- A) 10X8 O/A DUCT | | PENETRATING THE TRAINING/CORRIDOR WALL. B) 16X12 O/A | | DUCT PENETRATING THE TRAINING/CORRIDOR WALL, AND THE | | TRAINING/VESTIBULE/MEN'S RESTROOM WALLS. C) 8X8 SUPPLY | | DUCT PENETRATING THE COPY ROOM/ELEVATOR LOBBY WALL. | | | | 6) SUBMIT AN APPROVED FL. PRODUCT APPROVAL AND/OR | | MIAMI-DADE NOA FOR THE LOUVERS. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|