Plan Review Notes
Plan Review Notes For Permit 17040199
Permit Number 17040199
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2017-04-11 16:51:25THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1)
 SHEET A 0.01 - THERE INCORRECT REFERENCES INDICATED FOR
 THE CURRENT EDITIONS OF THE FLORIDA FIRE PREVENTION
 CODE.
  
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING
 THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER
 APPLICABLE CODES OR STANDARDS.
 FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 13, 2010 EDITION.
 FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 72, 2010 EDITION.
 CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 241, 2009 EDITION.
 FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 10, 2010 EDITION.
 ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2011 EDITION.
 EMERGENCY AND STANDBY POWER SYSTEMS SHALL COMPLY WITH
 NFPA 110, 2013 EDITION.
 AIR CONDITION WORK SHALL COMPLY WITH NFPA 90 A & B,
 2012 EDITION
  
 PLEASE CORRECT ALL THE APPLICABLE CODE EDITIONS.
  
  
  
 2)
 SHEETS A 0.0. & 0.03 - NOTE # 7 MAKES REFERENCE TO AND
 INCORRECT NFPA 13 EDITION.
  
 PLEASE CORRECT AS NOTED ON # 1 ABOVE.
  
  
  
  
 3)
 SHEET A 1.11 - THERE ARE INDICATIONS OF WALL TYPE
 REFERENCE OF A BOX AROUND, S1, TO WALLS CONTAINING FIRE
 RATED DOORS. ON SHEETS A 5.11 & 5.12 THERE ARE NO
 INDICATORS MATHCING THAT REFERENCE OR ANY OTHER LISTED
 WALL RATING.
  
 PLEASE PROVIDE THE APPLICABLE LISTED WALL RATING FOR
 THAT REFERENCE.
  
  
  
  
 4)
 SHEET A 0.02 & 0.03 - NOTE # 4 INDICATES REFERNCES TO
 LIFE SAFETY DEVICES ON THE ELECTICAL SHEETS. THERE ARE
 NO INDICATORS OF ANY FIRE ALARM DEVICES ON ANY
 ELECTICAL SHEET.
  
 ANY AND ALL WORK ON THE FIRE ALARM SYSTEM SHALL BE DONE
 UNDER SEPARATE SHOP DRAWINGS AND BY CERTIFIED LIFE
 SAFETY CONTRACTORS.
  
 THE FIRE ALARM SYSTEM SHALL REMAIN ACTIVE THROUGHOUT
 THE CONSTRUCTION PERIOD.
  
 PLEASE PROVIDE AN APLLICABLE NOTE.
  
  
  
 5)
 SHEET E - THE ELECTRICAL SHEETS INDICATE CARD READERS
 ON EXIT DOORS. THESE CARD READERS SHALL DELAY OR
 INTERFERE WITH ANY EXIT DOOR AND SHALL COMPLY WITH NFPA
 101, CHAPTER 7, MEANS OF EGRESS AND SHALL BE INSTALLED
 UNDER SEPARATE SHOP DRAWINGS.
  
 PLEASE PROVIDE AN APPLICABLE NOTE.
  
  
  
 6)
 SHEET A 0.01 - NOTE # 7 REFERENCES WORK ON THE FIRE
 SPRINKLER SYSTEMS. THE FIRE SPRINKLER SHALL REMAIN
 ACTIVE THROUGHOUT THE CONSTRUCTION PERIOD. ANY TIME
 THAT WORK ON THE FIRE SPRINKLER SYSTEM EXCEEDS 4 HOURS,
 A FIRE WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL
 FULL AND COMPLETE PROTECTION IS RETURNED.
  
 PLEASE PROVIDE AND APPLICABLE NOTE.
  
  
 7)
 SHEET A 0.02 & 0.03 - FOR INFORMATIONAL PURPOSES, THERE
 IS A MISSPELLED WORD; "OCCUYPANCY", INDICATED IN THE
 TABLE HEADER.
  
  
  
 8) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 9) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  