2017-04-11 16:51:25 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| |
| 1) |
| SHEET A 0.01 - THERE INCORRECT REFERENCES INDICATED FOR |
| THE CURRENT EDITIONS OF THE FLORIDA FIRE PREVENTION |
| CODE. |
| |
| THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE |
| 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING |
| THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER |
| APPLICABLE CODES OR STANDARDS. |
| FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS |
| OF NFPA 13, 2010 EDITION. |
| FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF |
| NFPA 72, 2010 EDITION. |
| CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF |
| NFPA 241, 2009 EDITION. |
| FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS |
| OF NFPA 10, 2010 EDITION. |
| ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2011 EDITION. |
| EMERGENCY AND STANDBY POWER SYSTEMS SHALL COMPLY WITH |
| NFPA 110, 2013 EDITION. |
| AIR CONDITION WORK SHALL COMPLY WITH NFPA 90 A & B, |
| 2012 EDITION |
| |
| PLEASE CORRECT ALL THE APPLICABLE CODE EDITIONS. |
| |
| |
| |
| 2) |
| SHEETS A 0.0. & 0.03 - NOTE # 7 MAKES REFERENCE TO AND |
| INCORRECT NFPA 13 EDITION. |
| |
| PLEASE CORRECT AS NOTED ON # 1 ABOVE. |
| |
| |
| |
| |
| 3) |
| SHEET A 1.11 - THERE ARE INDICATIONS OF WALL TYPE |
| REFERENCE OF A BOX AROUND, S1, TO WALLS CONTAINING FIRE |
| RATED DOORS. ON SHEETS A 5.11 & 5.12 THERE ARE NO |
| INDICATORS MATHCING THAT REFERENCE OR ANY OTHER LISTED |
| WALL RATING. |
| |
| PLEASE PROVIDE THE APPLICABLE LISTED WALL RATING FOR |
| THAT REFERENCE. |
| |
| |
| |
| |
| 4) |
| SHEET A 0.02 & 0.03 - NOTE # 4 INDICATES REFERNCES TO |
| LIFE SAFETY DEVICES ON THE ELECTICAL SHEETS. THERE ARE |
| NO INDICATORS OF ANY FIRE ALARM DEVICES ON ANY |
| ELECTICAL SHEET. |
| |
| ANY AND ALL WORK ON THE FIRE ALARM SYSTEM SHALL BE DONE |
| UNDER SEPARATE SHOP DRAWINGS AND BY CERTIFIED LIFE |
| SAFETY CONTRACTORS. |
| |
| THE FIRE ALARM SYSTEM SHALL REMAIN ACTIVE THROUGHOUT |
| THE CONSTRUCTION PERIOD. |
| |
| PLEASE PROVIDE AN APLLICABLE NOTE. |
| |
| |
| |
| 5) |
| SHEET E - THE ELECTRICAL SHEETS INDICATE CARD READERS |
| ON EXIT DOORS. THESE CARD READERS SHALL DELAY OR |
| INTERFERE WITH ANY EXIT DOOR AND SHALL COMPLY WITH NFPA |
| 101, CHAPTER 7, MEANS OF EGRESS AND SHALL BE INSTALLED |
| UNDER SEPARATE SHOP DRAWINGS. |
| |
| PLEASE PROVIDE AN APPLICABLE NOTE. |
| |
| |
| |
| 6) |
| SHEET A 0.01 - NOTE # 7 REFERENCES WORK ON THE FIRE |
| SPRINKLER SYSTEMS. THE FIRE SPRINKLER SHALL REMAIN |
| ACTIVE THROUGHOUT THE CONSTRUCTION PERIOD. ANY TIME |
| THAT WORK ON THE FIRE SPRINKLER SYSTEM EXCEEDS 4 HOURS, |
| A FIRE WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL |
| FULL AND COMPLETE PROTECTION IS RETURNED. |
| |
| PLEASE PROVIDE AND APPLICABLE NOTE. |
| |
| |
| 7) |
| SHEET A 0.02 & 0.03 - FOR INFORMATIONAL PURPOSES, THERE |
| IS A MISSPELLED WORD; "OCCUYPANCY", INDICATED IN THE |
| TABLE HEADER. |
| |
| |
| |
| 8) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| |
| |
| 9) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| |
| |