2017-04-13 12:54:46 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | | | 1. SCOPE NOT CLEAR. SEE PREVIOUS LIST; WORST CASE | | DESIGN PRESSURES ARE FOR ZONES 6 AND 7. THEY WERE NOT | | INCLUDED IN THE ENGINEERING. A ROOF PLAN WAS SUBMITTED | | WITH PORTIONS HIGHLIGHTED. ZONES 2 AND 3 ARE NOT | | HIGHLIGHTED FOR TWO LARGE PORTIONS OF ROOF AREA. DOES | | THIS MEAN YOU PROPOSE TO REROOF ONLY A PORTION OF THE | | ROOF, AND LEAVING THE EDGES AND CORNERS? DOESN'T THIS | | PROJECT INCLUDE AN ADDITION? FOR THE ADDITION AREA, | | ONLY ZONE 1 WAS HIGHLIGHTED. | | | | REVISE THE ROOF PLAN TO INCLUDE A LEGEND AS THE | | HIGHLIGHTING IS NOT CLEAR AS TO WHAT IT REPRESENTS. AS | | A PORTION IS OVER THE ADDITION, ALL ZONES (1, 2, 3) ARE | | REQUIRED. AS THE REROOF PORTION IS OVER 25% OF THE | | ROOF, A COMPLETE REROOF (ZONES 1, 2, 3) IS REQUIRED, | | FBC EB 708.1.1. | | | | 2. DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED FOR | | PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED ORIGINALS | | FS471. | | | | (RAS117 CALCULATIONS CHECKED AND ARE OK) | | | | | | | | |
|