Plan Review Notes
Plan Review Notes For Permit 17040081
Permit Number 17040081
Review Stop B
Sequence Number 2
Notes
Date Text
2017-04-13 12:54:46****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. SCOPE NOT CLEAR. SEE PREVIOUS LIST; WORST CASE
 DESIGN PRESSURES ARE FOR ZONES 6 AND 7. THEY WERE NOT
 INCLUDED IN THE ENGINEERING. A ROOF PLAN WAS SUBMITTED
 WITH PORTIONS HIGHLIGHTED. ZONES 2 AND 3 ARE NOT
 HIGHLIGHTED FOR TWO LARGE PORTIONS OF ROOF AREA. DOES
 THIS MEAN YOU PROPOSE TO REROOF ONLY A PORTION OF THE
 ROOF, AND LEAVING THE EDGES AND CORNERS? DOESN'T THIS
 PROJECT INCLUDE AN ADDITION? FOR THE ADDITION AREA,
 ONLY ZONE 1 WAS HIGHLIGHTED.
  
 REVISE THE ROOF PLAN TO INCLUDE A LEGEND AS THE
 HIGHLIGHTING IS NOT CLEAR AS TO WHAT IT REPRESENTS. AS
 A PORTION IS OVER THE ADDITION, ALL ZONES (1, 2, 3) ARE
 REQUIRED. AS THE REROOF PORTION IS OVER 25% OF THE
 ROOF, A COMPLETE REROOF (ZONES 1, 2, 3) IS REQUIRED,
 FBC EB 708.1.1.
  
 2. DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED FOR
 PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED ORIGINALS
 FS471.
  
 (RAS117 CALCULATIONS CHECKED AND ARE OK)
  
  
  
  