Plan Review Notes For Permit 17040081 |
Permit Number |
17040081 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-04-05 06:51:10 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | | | 1. THE ASSEMBLY PROPOSED HAS A DP OF -52.5 (GENERAL | | LIMITATION #9, CANNOT BE INCREASED). SEE PAGE S0.2, | | WORST CASE APPEARS TO BE -128.8, SEE SHEET S0.2, FBC | | 1609. (NOT ENTIRELY CLEAR AS "ULTIMATE" AND "ALLOWABLE" | | PRESSURES FOR ZONES 6 AND 7 ARE THE SAME) | | | | 2. PRODUCT APPROVALS AND ASSEMBLY PROPOSED ARE TO BE | | REVIEWED BY DESIGNER OF RECORD PRIOR TO SUBMITTAL, FBC | | 107. |
|