Plan Review Notes
Plan Review Notes For Permit 17040028
Permit Number 17040028
Review Stop M
Sequence Number 1
Notes
Date Text
2017-04-11 11:46:39PASS PROVISO
 1) PROVIDE A ENGINEER DETAIL ON CURB TO ROOF
 AND RTU TO CURB TIE DOWN. AT FIRST INSPECTION.
 PER SECTION 301.15 WIND RESISTANCE 2014 FBC (M)
 2) FAN SHUT DOWN REQUIRED FOR RTU 1 AND 2
 PER SECTION 606.2.1 RETURN AIR SYSTEM. 2014 FBC (M)
 3) REFER TO SECTION 606.4.1 SUPERVISION AND SECTION
 606.3 INSTALLATION 2014 FBC (M)
  