Plan Review Notes For Permit 17040017 |
Permit Number |
17040017 |
|
Review Stop |
R |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2017-06-29 16:53:52 | GAF BUR SYSTEM, NOA NO.13-1022.15 | | PROVISO: SPECIFY THE APPROVED ASSEMBLY, MAXIMUM DESIGN | | PRESSURE AND PROVIDE TWO SETS OF SIGNED AND SEALED RAS | | 117 CALCULATIONS FOR ENHANCED FASTENING AS REQUIRED BY | | LIMITATION #7 OF THE NOA. NOTE: THE PLANS SPECIFY 1" | | POLYISOCYANURATE INSULATION AS PART OF THE ROOFING | | ASSEMBLY. |
|