2017-05-04 11:51:51 | PLAN |
| REVIEW COMMENTS |
| |
| 1ST REVIEW: FBC FIFTH EDITION (2014) |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| DENIED BY BUILDING |
| PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| |
| 1) SUBMIT TWO SETS OF A SURFACE WATER DRAINAGE PLAN |
| THAT SHOWS COMPLIANCE WITH FBC-R 401.3 DRAINAGE. |
| SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER |
| CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT |
| DOES NOT CREATE A HAZARD. LOTS SHALL BE GRADED TO DRAIN |
| SURFACE WATER AWAY FROM FOUNDATION WALLS. THE GRADE |
| SHALL FALL A MINIMUM OF 6 INCHES (152 MM) WITHIN THE |
| FIRST 10 FEET (3048 MM). |
| |
| 2) THIS PROJECT IS UNDER THE 2014 FBC. THERE ARE |
| REFERENCES TO THE 2010 FBC UNDER THE STRUCTURAL NOTES |
| ON SHEET S.1. PLEASE REVISE. |
| |
| 3) SHOW COMPLIANCE WITH FBC-R318.1 FOR TERMITE |
| PROTECTION. |
| |
| 4) SHOW COMPLIANCE WITH FBC-R318.5 CONDENSATE LINES, |
| IRRIGATION/SPRINKLER SYSTEM RISERS FOR SPRAY HEADS, AND |
| ROOF DOWNSPOUTS SHALL DISCHARGE AT LEAST 1 FOOT (305 |
| MM) AWAY FROM THE STRUCTURE SIDEWALL, WHETHER BY |
| UNDERGROUND PIPING, TAIL EXTENSIONS OR SPLASH BLOCKS. |
| GUTTERS WITH DOWNSPOUTS ARE REQUIRED ON ALL BUILDINGS |
| WITH EAVES OF LESS THAN 6 INCHES (152 MM) HORIZONTAL |
| PROJECTION EXCEPT FOR GABLE END RAKES OR ON A ROOF |
| ABOVE ANOTHER ROOF. |
| |
| 5) THE PLANS DO NOT SPECIFY ANY REINFORCEMENT IN THE 4" |
| CONCRETE FLOOR SLAB. DUE TO THE SOIL CONDITIONS, IT IS |
| REQUIRED THAT THE SLAB IS LIGHTLY REINFORCED USING 6 X |
| 6 WELDED WIRE FABRIC. FBC-R506.1 & ACI 332 |
| |
| 6) SPECIFY THE SLOPE OF THE HIP ROOF ON THE PLANS. |
| FBC107.2.1 |
| |
| 7) PROVIDE WINDOW AND DOOR BUCK DETAILS ON THE PLANS. |
| |
| 8) PROVIDE STRUCTURAL DETAILS FOR THE LEDGERS THAT ARE |
| SUPPORTING THE ROOF TRUSSES. |
| |
| 9) PROVIDE THE ROOF UPLIFT VALUES FOR A 10 SQFT |
| EFFECTIVE WIND AREA. |
| |
| 10) IN THE TABLE ON SHEET S.3 THE ROOF UPLIFT VALUES |
| FOR ZONES 2 AND 3 ARE IDENTICAL. THE PARAPET IS |
| REQUIRED TO BE 3 FEET HIGH AROUND THE ENTIRE PERIMETER |
| OF THE ROOF IN ORDER FOR THE ZONE 2 (PERIMETER) |
| PRESSURES TO BE THE SAME AS THE ZONE 3 (CORNER) |
| PRESSURES. ACSE 7 - 10. |
| |
| 11) PROVIDE SCUPPER SIZING CALCULATIONS. FBC 107.2.1 & |
| FBC- PLUMBING 1106.7 |
| |
| 12) R903.4.1 OVERFLOW DRAINS AND SCUPPERS. WHEN OTHER |
| MEANS OF DRAINAGE OF OVERFLOW WATER IS NOT PROVIDED, |
| OVERFLOW SCUPPERS SHALL BE PLACED IN WALLS OR PARAPETS |
| NOT LESS THAN 2 INCHES (51 MM) NOR MORE THAN 4 INCHES |
| (102 MM) ABOVE THE FINISHED ROOF COVERING AND SHALL BE |
| LOCATED AS CLOSE AS PRACTICAL TO REQUIRED VERTICAL |
| LEADERS OR DOWNSPOUTS OR WALL AND PARAPET SCUPPERS. AN |
| OVERFLOW SCUPPER SHALL BE SIZED IN ACCORDANCE WITH THE |
| FLORIDA BUILDING CODE, PLUMBING. |
| |
| 13) THE PLANS SHOW LOUVERED WALL ATTIC VENTS ON SHEET |
| A.2 AND THE ENERGY FORM SPECIFIES AN UNVENTED ATTIC. |
| PLEASE CLARIFY FBC 107.2.1 |
| |
| 14) IF THE ATTIC IS VENTED PROVIDE THE NET FREE AREA OF |
| THE VENTS AND THE CALCULATIONS FOR MINIMUM VENT AREA |
| PER FBC - R806.2 |
| |
| 15) IF THIS IS AN UNVENTED ATTIC SHOW THAT IT COMPLIES |
| WITH FBC-R806.5 UNVENTED ATTIC AND UNVENTED ENCLOSED |
| RAFTER ASSEMBLIES. UNVENTED ATTIC ASSEMBLIES (SPACES |
| BETWEEN THE CEILING JOISTS OF THE TOP STORY AND THE |
| ROOF RAFTERS) AND UNVENTED ENCLOSED RAFTER ASSEMBLIES |
| (SPACES BETWEEN CEILINGS THAT ARE APPLIED DIRECTLY TO |
| THE UNDERSIDE OF ROOF FRAMING MEMBERS/RAFTERS AND THE |
| STRUCTURAL ROOF SHEATHING AT THE TOP OF THE ROOF |
| FRAMING MEMBERS/RAFTERS) SHALL BE PERMITTED IF ALL THE |
| FOLLOWING CONDITIONS ARE MET: |
| |
| 1. THE UNVENTED ATTIC SPACE IS COMPLETELY CONTAINED |
| WITHIN THE BUILDING THERMAL ENVELOPE. |
| |
| 2. NO INTERIOR CLASS I VAPOR RETARDERS ARE INSTALLED ON |
| THE CEILING SIDE (ATTIC FLOOR) OF THE UNVENTED ATTIC |
| ASSEMBLY OR ON THE CEILING SIDE OF THE UNVENTED |
| ENCLOSED RAFTER ASSEMBLY. |
| |
| 3. WHERE WOOD SHINGLES OR SHAKES ARE USED, A MINIMUM |
| 1/4- INCH (6 MM) VENTED AIR SPACE SEPARATES THE |
| SHINGLES OR SHAKES AND THE ROOFING UNDERLAYMENT ABOVE |
| THE STRUCTURAL SHEATHING. |
| |
| 4. IN CLIMATE ZONES 5, 6, 7 AND 8 OF TABLE R301.1 OF |
| THE FLORIDA BUILDING CODE, ENERGY CONSERVATION, ANY |
| AIRIMPERMEABLE INSULATION SHALL BE A CLASS II VAPOR |
| RETARDER, OR SHALL HAVE A CLASS III VAPOR RETARDER |
| COATING OR COVERING IN DIRECT CONTACT WITH THE |
| UNDERSIDE OF THE INSULATION. |
| |
| 5. EITHER ITEMS 5.1, 5.2 OR 5.3 SHALL BE MET, DEPENDING |
| ON THE AIR PERMEABILITY OF THE INSULATION DIRECTLY |
| UNDER THE STRUCTURAL ROOF SHEATHING. |
| |
| 5.1. AIR-IMPERMEABLE INSULATION ONLY. INSULATION SHALL |
| BE APPLIED IN DIRECT CONTACT WITH THE UNDERSIDE OF THE |
| STRUCTURAL ROOF SHEATHING. |
| |
| 5.2. AIR-PERMEABLE INSULATION ONLY. IN ADDITION TO THE |
| AIR-PERMEABLE INSULATION INSTALLED DIRECTLY BELOW THE |
| STRUCTURAL SHEATHING, RIGID BOARD OR SHEET INSULATION |
| SHALL BE INSTALLED DIRECTLY ABOVE THE STRUCTURAL ROOF |
| SHEATHING AS SPECIFIED IN TABLE R806.5 FOR CONDENSATION |
| CONTROL. |
| |
| 5.3. AIR-IMPERMEABLE AND AIR-PERMEABLE INSULATION. THE |
| AIR-IMPERMEABLE INSULATION SHALL BE APPLIED IN DIRECT |
| CONTACT WITH THE UNDERSIDE OF THE STRUCTURAL ROOF |
| SHEATHING AS SPECIFIED IN TABLE R806.5 FOR CONDENSATION |
| CONTROL. THE AIR-PERMEABLE INSULATION SHALL BE |
| INSTALLED DIRECTLY UNDER THE AIR-IMPERMEABLE |
| INSULATION. |
| |
| 5.4. WHERE PREFORMED INSULATION BOARD IS USED AS THE |
| AIR-IMPERMEABLE INSULATION LAYER, IT SHALL BE SEALED AT |
| THE PERIMETER OF EACH INDIVIDUAL SHEET INTERIOR SURFACE |
| TO FORM A CONTINUOUS LAYER. |
| |
| 16) SUBMIT THE PRODUCT EVALUATION REPORT OF THE SPRAY |
| FOAM INSULATION (IF APPLICABLE). FBC-R316 |
| |
| 17) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS |
| FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC |
| 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE |
| BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER |
| OF RECORD. PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH |
| FL OR NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS |
| AND MAXIMUM DESIGN PRESSURES FOR EACH OF THE DIFFERENT |
| ROOFING MATERIALS, AND THE CASEMENT WINDOWS. |
| |
| 18) SUBMIT AN ADDITIONAL SET OF PRODUCT APPROVALS FOR |
| THE ONES THAT WERE SUBMITTED. TWO SETS ARE REQUIRED. |
| FBC 107.3.4 |
| |
| 19) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT |
| A RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW |
| COMMENTS HAS BEEN ADDRESSED. |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |