2017-11-13 08:20:02 | BUILDING PLAN REVIEW |
| W. P. B. REVISION: 17031256 |
| W. P. B. PERMIT: 16050258 |
| ADD: 209 6TH ST. |
| CONT: OWNER BUILDER ALLIANCES |
| TEL: 561-254-6779 |
| E-MAIL: [email protected], |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 4TH REVIEW |
| DATE: MON. NOV. 13/2017 |
| ACTION: DENIED |
| |
| 1-3A) COMPLIED. |
| |
| 3B) THE CONTRACTOR STATES THE STORM SHUTTER IS GOING TO |
| BE ATTACHED HORIZONTALLY BUT PLEASE NOTE THE END POST |
| CLOSEST THE MAIN STRUCTURE IS A 6X6 INCH STEEL POST. |
| THE SUBMITTED PRODUCT APPROVAL DOES NOT HAVE DETAILS |
| FOR FASTENING TO A STEEL COLUMN. THE STRUCTURAL |
| ENGINEER WILL NEED TO PROVIDE HOW COMPLIANCE WILL BE |
| ACHIEVED. 107.2.1.3 ADDITIONAL INFORMATION REQUIRED. |
| |
| 3C) 4TH REQUEST. PLEASE NOTE SHEET S-1 SHOWS A COLUMN |
| SCHEDULE. THE SCHEDULE SHOWS BOTH COLUMNS SC1 & SC2 TO |
| BE 6 X 6 INCH STEEL COLUMNS. SC3 IS TO BE 3 X 3 INCH |
| STEEL COLUMNS NOWHERE IN THE STEEL COLUMN SCHEDULE HAS |
| IT BEEN UPDATED TO WOOD COLUMNS. UPDATE PLANS |
| DISCREPANCY IN PLANS. 107.2.1.3 ADDITIONAL INFORMATION |
| REQUIRED. |
| |
| 3D) SHEET S-2 SEMI COMPLIED. THERE IS ONLY ONE SET OF |
| SUBMITTED PLANS WITH A UPDATED (10-19-17). THE OTHER |
| SET HAS (2) S-5 SHEETS DATED (10-19-17). |
| |
| 3D) PLEASE BE AWARE, THE DESIGN GIVEN THE 6X6 WOOD POST |
| HAS NOT SPECIFIED A TYPE OF WOOD GRADE OF WOOD OR |
| DENSITY WHICH ARE REQUIRED BY THE PRODUCT APPROVAL |
| WHERE THE STORM SHUTTERS ARE TO BE ANCHORED INTO WOOD |
| FRAMING. REQUIRED INFORMATION. 107.2.1.3 ADDITIONAL |
| INFORMATION REQUIRED. |
| |
| 4) COMPLIED. |
| |
| 5) COLLATE PLANS INTO COMPLETE SETS OF DOCUMENTS. |
| SUBMITTED 2 DIFFERENT PRODUCT APPROVALS VOID OUT THE |
| ONE NOT BEING USED> WHEN RESUBMITTING PLANS PLEASE |
| INDICATE THE REVISION & REMOVE ANY VOIDED SHEETS & |
| REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH A |
| DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE SHEET |
| OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| ANTICIPATED COOPERATION. |
| |