Plan Review Notes
Plan Review Notes For Permit 17031256
Permit Number 17031256
Review Stop B
Sequence Number 4
Notes
Date Text
2017-11-13 08:20:02BUILDING PLAN REVIEW
 W. P. B. REVISION: 17031256
 W. P. B. PERMIT: 16050258
 ADD: 209 6TH ST.
 CONT: OWNER BUILDER ALLIANCES
 TEL: 561-254-6779
 E-MAIL: [email protected],
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 4TH REVIEW
 DATE: MON. NOV. 13/2017
 ACTION: DENIED
  
 1-3A) COMPLIED.
  
 3B) THE CONTRACTOR STATES THE STORM SHUTTER IS GOING TO
 BE ATTACHED HORIZONTALLY BUT PLEASE NOTE THE END POST
 CLOSEST THE MAIN STRUCTURE IS A 6X6 INCH STEEL POST.
 THE SUBMITTED PRODUCT APPROVAL DOES NOT HAVE DETAILS
 FOR FASTENING TO A STEEL COLUMN. THE STRUCTURAL
 ENGINEER WILL NEED TO PROVIDE HOW COMPLIANCE WILL BE
 ACHIEVED. 107.2.1.3 ADDITIONAL INFORMATION REQUIRED.
  
 3C) 4TH REQUEST. PLEASE NOTE SHEET S-1 SHOWS A COLUMN
 SCHEDULE. THE SCHEDULE SHOWS BOTH COLUMNS SC1 & SC2 TO
 BE 6 X 6 INCH STEEL COLUMNS. SC3 IS TO BE 3 X 3 INCH
 STEEL COLUMNS NOWHERE IN THE STEEL COLUMN SCHEDULE HAS
 IT BEEN UPDATED TO WOOD COLUMNS. UPDATE PLANS
 DISCREPANCY IN PLANS. 107.2.1.3 ADDITIONAL INFORMATION
 REQUIRED.
  
 3D) SHEET S-2 SEMI COMPLIED. THERE IS ONLY ONE SET OF
 SUBMITTED PLANS WITH A UPDATED (10-19-17). THE OTHER
 SET HAS (2) S-5 SHEETS DATED (10-19-17).
  
 3D) PLEASE BE AWARE, THE DESIGN GIVEN THE 6X6 WOOD POST
 HAS NOT SPECIFIED A TYPE OF WOOD GRADE OF WOOD OR
 DENSITY WHICH ARE REQUIRED BY THE PRODUCT APPROVAL
 WHERE THE STORM SHUTTERS ARE TO BE ANCHORED INTO WOOD
 FRAMING. REQUIRED INFORMATION. 107.2.1.3 ADDITIONAL
 INFORMATION REQUIRED.
  
 4) COMPLIED.
  
 5) COLLATE PLANS INTO COMPLETE SETS OF DOCUMENTS.
 SUBMITTED 2 DIFFERENT PRODUCT APPROVALS VOID OUT THE
 ONE NOT BEING USED> WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE ANY VOIDED SHEETS &
 REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  