2017-08-31 14:14:28BUILDING PLAN REVIEW
 W. P. B. REVISION: 17031256
 W. P. B. PERMIT: 16050258
 ADD: 209 6TH ST.
 CONT: OWNER BUILDER ALLIANCES
 TEL: 561-254-6779
 E-MAIL: [email protected],
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: THURS. AUGUST 31/2017
 ACTION: DENIED
  
 1) SEMI-COMPLIED. SHOP DRAWING OF APPROVAL ON THE
 PRODUCT APPROVAL. NEITHER THE CONTRACTOR NOR THE
 DESIGNER OF RECORD HAS COMPLIED WITH REQUIREMENT # 3
 IDENTIFYING THE SYSTEM IN THE PRODUCT APPROVAL. WHICH
 CONFIGURATION OF PANELS, TRACK SYSTEMS, AND ASSOCIATED
 HARDWARE. SHEETS 11-14 OF THE TECHNICAL SHEETS ARE FOR
 WOOD STRUCTURES.
  
  
 2ND ROUND OF COMMENTS. IF THE CONTRACTOR (BEELINE
 BUILDING CORP) IS LOOKING FOR COMPLETING OF ENCLOSURE
 OF THE COOLER AND FREEZERS WITH THE USE OF HURRICANE
 PANELS THE DESIGNER OF RECORD WILL NEED TO APPLY THEIR
 SHOP DRAWING STAMP OF APPROVAL ON THE PRODUCT APPROVAL.
 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS WHICH
 ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR
 TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. FL
 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 2) COMPLIED. FLORIDA APPROVAL FL1968-R3
  
 3) PLEASE NOTE THE CONTRACTOR STATES THE STORM PANELS
 ARE GOING TO BE PLACED HORIZONTALLY BUT NOWHERE IS
 THERE AN INSTALLATION SCHEDULE REPEAT FROM THE LAST
 REVIEW!!!!!
  
 3B) THE CONTRACTOR STATES THE STORM SHUTTER IS GOING TO
 BE ATTACHED HORIZONTALLY BUT PLEASE NOTE THE END POST
 CLOSEST THE MAIN STRUCTURE IS A 6X6 INCH STEEL POST.
 THE SUBMITTED PRODUCT APPROVAL DOES NOT HAVE DETAILS
 FOR FASTENING TO A STEEL COLUMN. THE STRUCTURAL
 ENGINEER WILL NEED TO PROVIDE HOW COMPLIANCE WILL BE
 ACHIEVED. 107.2.1.3 ADDITIONAL INFORMATION REQUIRED.
  
 3C) PLEASE NOTE SHEET S-1 SHOWS A COLUMN SCHEDULE. THE
 SCHEDULE SHOWS BOTH COLUMNS SC1 & SC2 TO BE 6 X 6 INCH
 STEEL COLUMNS. SC3 IS TO BE 3 X 3 INCH STEEL COLUMNS
 NOWHERE IN THE STEEL COLUMN SCHEDULE HAS IT BEEN
 UPDATED TO WOOD COLUMNS. UPDATE PLANS DISCREPANCY IN
 PLANS. 107.2.1.3 ADDITIONAL INFORMATION REQUIRED.
  
  
 3D) SHEET S-2 DOES NOT PROVIDE WHAT THE CENTER TO
 CENTER LAYOUT OF THE 6 X 6 INCH WOOD POST ARE CENTERED,
 NOR DOES THE PLAN OR STORM SHUTTER SCHEDULE INDICATE
 THE PRESSURES GIVEN ARE LIMITED TO NINE FEET. THE
 STRUCTURAL SHEET S-2 NEEDS TO BE UPDATED. 107.2.1.3
 ADDITIONAL INFORMATION REQUIRED.
  
 3D) PLEASE BEWARE, THE DESIGN GIVEN THE 6X6 WOOD POST
 HAS NOT SPECIFIED A TYPE OF WOOD GRADE OF WOOD OR
 DENSITY WHICH ARE REQUIRED BY THE PRODUCT APPROVAL
 WHERE THE STORM SHUTTERS ARE TO BE ANCHORED INTO WOOD
 FRAMING. REQUIRED INFORMATION. 107.2.1.3 ADDITIONAL
 INFORMATION REQUIRED.
  
 2ND ROUND COMMENT. WITHIN THE PRODUCT APPROVAL
 SUBMITTED THERE IS DETAILS FOR ANCHORING TO CONCRETE
 FOR BOTH THE TOP AND BOTTOM TRACKS, AND FOR WOOD. THE
 SUBMITTED STRUCTURAL SHEETS SHOWS A CONCRETE SLAB AND A
 STEEL HORIZONTAL BEAM WITH METAL SCREED BENT PLATE
 1/4X4X3 INCH WELDED TO THE BEAM. WITHIN THIS PRODUCT
 APPROVAL THERE IS NO DETAILS NOR TABLE FOR ANCHOR
 SPACING. PLEASE PROVIDE : A COMPLETE INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING OPENING SIZES, UNIT
 MARK NUMBERS, UNIT SPANS/WIDTHS, IF STORM BAR
 REINFORCING REQUIREMENTS ARE REQUIRED, WALL PRESSURE
 ZONES, SLAT TYPES, GAUGE OF PANELS, ETC.
  
 4)3RD REQUEST. NOT ADDRESSED. COMMENT FROM THE LAST
 REVIEW IS NOT ADDRESSED. WITH THE STORM PANELS IN
 PLACE, HOW WILL THE CONDENSING UNITS DISSIPATE THE HEAT
 IF WITHIN THE ENCLOSED ROOM? 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  