2017-08-31 14:14:28 | BUILDING PLAN REVIEW |
| W. P. B. REVISION: 17031256 |
| W. P. B. PERMIT: 16050258 |
| ADD: 209 6TH ST. |
| CONT: OWNER BUILDER ALLIANCES |
| TEL: 561-254-6779 |
| E-MAIL: [email protected], |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 3RD REVIEW |
| DATE: THURS. AUGUST 31/2017 |
| ACTION: DENIED |
| |
| 1) SEMI-COMPLIED. SHOP DRAWING OF APPROVAL ON THE |
| PRODUCT APPROVAL. NEITHER THE CONTRACTOR NOR THE |
| DESIGNER OF RECORD HAS COMPLIED WITH REQUIREMENT # 3 |
| IDENTIFYING THE SYSTEM IN THE PRODUCT APPROVAL. WHICH |
| CONFIGURATION OF PANELS, TRACK SYSTEMS, AND ASSOCIATED |
| HARDWARE. SHEETS 11-14 OF THE TECHNICAL SHEETS ARE FOR |
| WOOD STRUCTURES. |
| |
| |
| 2ND ROUND OF COMMENTS. IF THE CONTRACTOR (BEELINE |
| BUILDING CORP) IS LOOKING FOR COMPLETING OF ENCLOSURE |
| OF THE COOLER AND FREEZERS WITH THE USE OF HURRICANE |
| PANELS THE DESIGNER OF RECORD WILL NEED TO APPLY THEIR |
| SHOP DRAWING STAMP OF APPROVAL ON THE PRODUCT APPROVAL. |
| FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS WHICH |
| ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE REVIEWED |
| AND APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR |
| TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. FL |
| 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP DRAWINGS ETC.. |
| |
| 2) COMPLIED. FLORIDA APPROVAL FL1968-R3 |
| |
| 3) PLEASE NOTE THE CONTRACTOR STATES THE STORM PANELS |
| ARE GOING TO BE PLACED HORIZONTALLY BUT NOWHERE IS |
| THERE AN INSTALLATION SCHEDULE REPEAT FROM THE LAST |
| REVIEW!!!!! |
| |
| 3B) THE CONTRACTOR STATES THE STORM SHUTTER IS GOING TO |
| BE ATTACHED HORIZONTALLY BUT PLEASE NOTE THE END POST |
| CLOSEST THE MAIN STRUCTURE IS A 6X6 INCH STEEL POST. |
| THE SUBMITTED PRODUCT APPROVAL DOES NOT HAVE DETAILS |
| FOR FASTENING TO A STEEL COLUMN. THE STRUCTURAL |
| ENGINEER WILL NEED TO PROVIDE HOW COMPLIANCE WILL BE |
| ACHIEVED. 107.2.1.3 ADDITIONAL INFORMATION REQUIRED. |
| |
| 3C) PLEASE NOTE SHEET S-1 SHOWS A COLUMN SCHEDULE. THE |
| SCHEDULE SHOWS BOTH COLUMNS SC1 & SC2 TO BE 6 X 6 INCH |
| STEEL COLUMNS. SC3 IS TO BE 3 X 3 INCH STEEL COLUMNS |
| NOWHERE IN THE STEEL COLUMN SCHEDULE HAS IT BEEN |
| UPDATED TO WOOD COLUMNS. UPDATE PLANS DISCREPANCY IN |
| PLANS. 107.2.1.3 ADDITIONAL INFORMATION REQUIRED. |
| |
| |
| 3D) SHEET S-2 DOES NOT PROVIDE WHAT THE CENTER TO |
| CENTER LAYOUT OF THE 6 X 6 INCH WOOD POST ARE CENTERED, |
| NOR DOES THE PLAN OR STORM SHUTTER SCHEDULE INDICATE |
| THE PRESSURES GIVEN ARE LIMITED TO NINE FEET. THE |
| STRUCTURAL SHEET S-2 NEEDS TO BE UPDATED. 107.2.1.3 |
| ADDITIONAL INFORMATION REQUIRED. |
| |
| 3D) PLEASE BEWARE, THE DESIGN GIVEN THE 6X6 WOOD POST |
| HAS NOT SPECIFIED A TYPE OF WOOD GRADE OF WOOD OR |
| DENSITY WHICH ARE REQUIRED BY THE PRODUCT APPROVAL |
| WHERE THE STORM SHUTTERS ARE TO BE ANCHORED INTO WOOD |
| FRAMING. REQUIRED INFORMATION. 107.2.1.3 ADDITIONAL |
| INFORMATION REQUIRED. |
| |
| 2ND ROUND COMMENT. WITHIN THE PRODUCT APPROVAL |
| SUBMITTED THERE IS DETAILS FOR ANCHORING TO CONCRETE |
| FOR BOTH THE TOP AND BOTTOM TRACKS, AND FOR WOOD. THE |
| SUBMITTED STRUCTURAL SHEETS SHOWS A CONCRETE SLAB AND A |
| STEEL HORIZONTAL BEAM WITH METAL SCREED BENT PLATE |
| 1/4X4X3 INCH WELDED TO THE BEAM. WITHIN THIS PRODUCT |
| APPROVAL THERE IS NO DETAILS NOR TABLE FOR ANCHOR |
| SPACING. PLEASE PROVIDE : A COMPLETE INSTALLATION |
| SCHEDULE SUMMARIZING & IDENTIFYING OPENING SIZES, UNIT |
| MARK NUMBERS, UNIT SPANS/WIDTHS, IF STORM BAR |
| REINFORCING REQUIREMENTS ARE REQUIRED, WALL PRESSURE |
| ZONES, SLAT TYPES, GAUGE OF PANELS, ETC. |
| |
| 4)3RD REQUEST. NOT ADDRESSED. COMMENT FROM THE LAST |
| REVIEW IS NOT ADDRESSED. WITH THE STORM PANELS IN |
| PLACE, HOW WILL THE CONDENSING UNITS DISSIPATE THE HEAT |
| IF WITHIN THE ENCLOSED ROOM? 107.2.1.3 ADDITIONAL |
| INFORMATION IS REQUIRED. |
| |
| 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |