Plan Review Notes For Permit 17031256 |
Permit Number |
17031256 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2017-06-13 14:00:25 | 1ST REVIEW FBC-2014 MECHANICAL | | PERMIT #17031256 | | 6/13/17 | | | | 1) THE NEW REMOTE "OUTDOOR CONDENSING UNITS" CANNOT BE | | INSTALLED IN AN ENCLOSED BUILDING UNLESS THE | | MANUFACTURER'S CERTIFIES THE INSTALLATION WITH | | SPECIFICATIONS AND INSTRUCTIONS. AT A MINIMUM | | VENTILATION IN SOME MANNER WOULD HAVE TO BE PROVIDED, | | HOWEVER NO VENTILATION SYSTEMS ARE SHOWN ON THE PLANS. | | LOOKING AT THE STRUCTURAL DRAWINGS, IT APPEARS TO BE | | COMPLETELY ENCLOSED | | WITH NO OPENINGS, INCLUDING NO ENTRY DOOR WHICH IS ALSO | | PUZZLING. | | | | 2) ME-2, NOTE #06: CONDENSATE SHALL NOT DRAIN INTO THE | | CITY SANITARY SYSTEM PER SECTION 90-126 WPB CODE OF | | ORDINANCES. CLARIFY IF THE HUB DRAIN IS CONNECTED TO A | | STORM DRAIN OR THE SANITARY. | | | | 3) TWO STRUCTURAL PLAN SHEETS HAVE BEEN SUBMITTED FOR | | THE NEW BUILDING ADDITION- SHEETS S2 & S3. IS THERE AN | | S1 COVER SHEET THAT WAS NOT SUBMITTED? THERE IS NO CODE | | DATA OR WIND LOAD DESIGN CRITERIA PROVIDED ON THE TWO | | SUBMITTED SHEETS. | | | | 4) SHEET S2: THE PLAN APPEARS TO SHOW THE WALK-IN BOXES | | VIRTUALLY FLUSH WITH THE ADDITION WALLS. HOW WILL | | ACCESS BE PROVIDED FOR CLEANING AND MAINTENANCE? | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|