Plan Review Notes
Plan Review Notes For Permit 17031256
Permit Number 17031256
Review Stop M
Sequence Number 2
Notes
Date Text
2017-06-13 14:00:251ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17031256
 6/13/17
  
 1) THE NEW REMOTE "OUTDOOR CONDENSING UNITS" CANNOT BE
 INSTALLED IN AN ENCLOSED BUILDING UNLESS THE
 MANUFACTURER'S CERTIFIES THE INSTALLATION WITH
 SPECIFICATIONS AND INSTRUCTIONS. AT A MINIMUM
 VENTILATION IN SOME MANNER WOULD HAVE TO BE PROVIDED,
 HOWEVER NO VENTILATION SYSTEMS ARE SHOWN ON THE PLANS.
 LOOKING AT THE STRUCTURAL DRAWINGS, IT APPEARS TO BE
 COMPLETELY ENCLOSED
 WITH NO OPENINGS, INCLUDING NO ENTRY DOOR WHICH IS ALSO
 PUZZLING.
  
 2) ME-2, NOTE #06: CONDENSATE SHALL NOT DRAIN INTO THE
 CITY SANITARY SYSTEM PER SECTION 90-126 WPB CODE OF
 ORDINANCES. CLARIFY IF THE HUB DRAIN IS CONNECTED TO A
 STORM DRAIN OR THE SANITARY.
  
 3) TWO STRUCTURAL PLAN SHEETS HAVE BEEN SUBMITTED FOR
 THE NEW BUILDING ADDITION- SHEETS S2 & S3. IS THERE AN
 S1 COVER SHEET THAT WAS NOT SUBMITTED? THERE IS NO CODE
 DATA OR WIND LOAD DESIGN CRITERIA PROVIDED ON THE TWO
 SUBMITTED SHEETS.
  
 4) SHEET S2: THE PLAN APPEARS TO SHOW THE WALK-IN BOXES
 VIRTUALLY FLUSH WITH THE ADDITION WALLS. HOW WILL
 ACCESS BE PROVIDED FOR CLEANING AND MAINTENANCE?
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  