2017-07-20 16:24:34 | BUILDING PLAN REVIEW |
| W. P. B. REVISION: 17031256 |
| W. P. B. PERMIT: 16050258 |
| ADD: 209 6TH ST. |
| CONT: OWNER BUILDER ALLIANCES |
| TEL: 561-254-6779 |
| E-MAIL: [email protected], |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 2ND REVIEW |
| DATE: THURS. JULY 20/2017 |
| ACTION: DENIED |
| |
| 1) IF THE CONTRACTOR (BEELINE BUILDING CORP) IS LOOKING |
| FOR COMPLETING OF ENCLOSURE OF THE COOLER AND FREEZERS |
| WITH THE USE OF HURRICANE PANELS THE DESIGNER OF RECORD |
| WILL NEED TO APPLY THEIR SHOP DRAWING STAMP OF APPROVAL |
| ON THE PRODUCT APPROVAL. |
| FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS WHICH |
| ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE REVIEWED |
| AND APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR |
| TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. FL |
| 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP DRAWINGS ETC.. |
| |
| 2) THE 2ND ISSUE WITH THE SUBMITTED EASTERN METAL |
| BERTHA ALUMINUM STORM PANELS, THERE IS NO COVER SHEET |
| INDICATING IF THE SUBMITTED APPROVAL IS A MIAMI-DADE |
| NOA OR A FLORIDA APPROVAL. PLEASE IDENTIFY SO |
| COMPLIANCE CAN BE VERIFIED. 1609.6.4.4.1 COMPONENTS & |
| CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, |
| ADMINISTRATIVE CODE 61G20-3.005 (31) SUB-CATEGORY OF |
| PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE |
| PRODUCT APPROVALS: (E) SHUTTERS. |
| |
| 3) WITHIN THE PRODUCT APPROVAL SUBMITTED THERE IS |
| DETAILS FOR ANCHORING TO CONCRETE FOR BOTH THE TOP AND |
| BOTTOM TRACKS, AND FOR WOOD. THE SUBMITTED STRUCTURAL |
| SHEETS SHOWS A CONCRETE SLAB AND A STEEL HORIZONTAL |
| BEAM WITH METAL SCREED BENT PLATE 1/4X4X3 INCH WELDED |
| TO THE BEAM. WITHIN THIS PRODUCT APPROVAL THERE IS NO |
| DETAILS NOR TABLE FOR ANCHOR SPACING. PLEASE PROVIDE : |
| A COMPLETE INSTALLATION SCHEDULE SUMMARIZING & |
| IDENTIFYING OPENING SIZES, UNIT MARK NUMBERS, UNIT |
| SPANS/WIDTHS, IF STORM BAR REINFORCING REQUIREMENTS ARE |
| REQUIRED, WALL PRESSURE ZONES, SLAT TYPES, GAUGE OF |
| PANELS, ETC. |
| |
| 4) COMMENT FROM THE LAST REVIEW IS NOT ADDRESSED. WITH |
| THE STORM PANELS IN PLACE, HOW WILL THE CONDENSING |
| UNITS DISSIPATE THE HEAT IF WITHIN THE ENCLOSED ROOM? |
| 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED. |
| |
| 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| CONSTRUCTION SERVICES DIVISION |
| DEVELOPMENT SERVICES DEPARTMENT |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |