2017-06-22 13:18:42 | BUILDING PLAN REVIEW |
| W. P. B. REVISION: 17031256 |
| W. P. B. PERMIT: 16050258 |
| ADD: 209 6TH ST. |
| CONT: OWNER BUILDER ALLIANCES |
| TEL: 561-254-6779 |
| E-MAIL: [email protected], |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 2ND REVIEW |
| DATE: FRI. JULY 22/2016 |
| ACTION: DENIED |
| |
| 1) THE SUBMITTED COOLER/ FREEZER PLANS DO NOT HAVE |
| APPROVAL FOR THE EXTERIOR OF THE BUILDING. IF SO PLEASE |
| SUBMIT STATE APPROVAL. THIS HAS BEEN VERIFIED BY THE |
| MECHANICAL PLAN REVIEWER THIS MANUFACTURER HAS NO STATE |
| APPROVAL FOR THE COOLER/ FREEZER UNITS FOR EXTERNAL |
| USE. PLEASE NOTE THE S2 & S3 SHEETS DO NOT PROVIDE |
| ENOUGH DETAILS. SHEET S2 HAS A CUT SECTION 9/S3 SHOWN |
| FOR BOTH THE EAST AND WEST ELEVATIONS SHOWING THE WALLS |
| ENCLOSED AND BENEATH THE ROOF STRUCTURE, AND 2 LAYERS |
| OF BOARD ON BOARD SCREEN WALL. |
| IT WOULD APPEAR THERE ARE NO OPENINGS TO ENTER THIS |
| MECHANICAL ROOM. I?VE GONE TO THE APPROVE PLANS FOR |
| VERIFICATION OF WHAT WAS APPROVED. SHEET A001.1 SHOWS |
| THE WEST FACE OF THE STRUCTURE IS TO BE 5 FT. -1 IN. |
| FROM THE PROPERTY LINE. SHEET A008 SHOWS THE EAST, |
| NORTH AND WEST ELEVATIONS OF THIS AREA. THE EAST WALL |
| DOES SHOW AN OPENING AS LARGE AS A GARAGE DOOR. THE |
| NORTH WALL NO OPENINGS, AND THE WEST WALL AS OPEN. THIS |
| IS A CODE VIOLATION; THE PLANS SHOULD NOT HAVE BEEN |
| ISSUED WITH THE WEST FACE OPEN. SINCE THE STRUCTURE IS |
| 5 FT. 1 INCH FROM THE PROPERTY LINE THIS WALL SHOULD BE |
| 1 HOUR RATED. THIS IS PROTECT THIS PROPERTY AS WELL AS |
| THE NEIGHBORING PROPERTY FROM FIRE, SEE 2014 FBC-B |
| TABLE 602 FOR ALL BUILDING TYPES AND OCCUPANCIES. |
| |
| THE OTHER ISSUE THAT WOULD NEED TO BE ADDRESSED SINCE |
| THE PLANS DO NOT STATE IF THIS STRUCTURE IS DESIGNED AS |
| AN ENCLOSED OR PARTIALLY ENCLOSED STRUCTURE. SHEET S1 |
| INDICATES THE MAIN BUILDING TO BE DESIGNED AS AN |
| ENCLOSED STRUCTURE. 2014 FBC-B 1603.1.4 WIND DESIGN |
| DATA. (4). APPLICABLE PRESSURE COEFFICIENT. PLEASE NOTE |
| IF THE ENCLOSURE IS OPEN OR PARTIALLY OPEN THEN THE |
| COOLER/ FREEZERS WILL HAVE TO HAVE BEEN TESTED FOR |
| THESE CONDITIONS!!!!! |
| |
| IF THE DESIGNER ELECTS TO ENCLOSE THE STRUCTURE WITH A |
| DOOR SYSTEM THEN AS STATED BY THE MECHANICAL REVIEWER |
| AIR CIRCULATION AND VENTING MAYBE A CONCERN IF THE |
| CONDENSERS ARE LOCATED WITHIN THIS ENCLOSED SPACE, |
| LOUVERS AND NEED TO BE CONSIDERED AND PRODUCT APPROVALS |
| . 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA |
| DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE |
| 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY |
| OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE |
| PRODUCT APPROVALS: ( C ) WALL LOVERS. |
| |
| 2) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |